Temperature source
Selects the source of the temperature reading used to adjust the speed of sound.
Index
Options
For more information, see Temperature source (2.11.1.4.) (Page 219).
Fixed Temperature
Sets the temperature of the source when there is no temperature-sensing device connected.
This parameter only displays if Fixed Temperature is selected for Temperature Source.
Value
Units
Sensor measurement units
Options
Note
For the purpose of this example, all values are assumed to be in meters.
Empty
Sets the distance from the face of the transducer to the process empty point
Index
Values
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
Transducer
*AUTO
Fixed Temperature
Transducer
External TS-3
Average of Sensors
Range: -100.0 ... +150.0 °C
Default: +20.0 °C
*M (meters)
CM (centimeters)
MM (millimeters)
FT (feet)
IN (inches)
Level
Range: 0.000 ... 99.000 m
Preset: 5.000 m
Commissioning
6.5 Quick Start Wizards