Siemens HydroRanger 200 HMI Operating Instructions Manual page 103

Sitrans ultrasonic controllers
Hide thumbs Also See for HydroRanger 200 HMI:
Table of Contents

Advertisement

Wet Well 2
Pump down with the following level and rate settings:
Parameter
Relay Function
(2.8.1.4.)
(Page 195)
ON Setpoint
(2.8.1.5.)
(Page 197)
OFF Setpoint
(2.8.1.6.)
(Page 197)
Pump by Rate
(2.8.1.8.)
(Page 198)
Pump by Rate (2.8.1.8.) (Page 198) sets the pump relays to accept control by rate of level change
once the first ON setpoint is reached. Because the pumps are started by rate, you must change Emp-
tying Indicator (2.3.10.) (Page 199) to desired empty rate.
Reservoir 1
Pump up with the following level settings:
Parameter
Relay Function (2.8.1.4.)
(Page 195)
ON Setpoint (2.8.1.5.)
(Page 197)
OFF Setpoint (2.8.1.6.)
(Page 197)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
Relay #
1
2
Alternate Duty
Alternate Duty
Assist
Assist
70%
80%
20%
20%
ON
Relay #
1
2
Alternate Duty
Alternate Duty
Assist
Assist
30%
20%
80%
80%
3
4
Level (H)
Level (L)
90%
10%
85%
15%
3
4
Level (H)
Level (L) OFF
90%
10%
85%
15%
Operating
7.3 Relays
5
6
OFF
OFF
--
--
--
--
5
6
OFF
--
--
--
--
101