Pump control reference
B.9 Service Ratio Duty Assist
B.9

Service Ratio Duty Assist

Relay function (2.8.1.4.) (Page 195) =
based on number of hours each pump has run and the specified ratios that each pump
requires. Multiple pumps can run at one time.
Relay operation
(for Relay logic (2.8.1.11.) (Page 199) = Positive)
The setpoints associated with the relays are grouped so they can be redistributed based on
pump RUN time ratios. The next pump to start or stop is the one with the required time to
actual time ratio.
Over time, the number of hours demanded of each pump will conform to the ratios specified.
Usually, the ratios are specified in percent values.
To create a grouping of pumps where two pumps make up 50 % of the run time and the third
pump makes up the other 50 %, Service ratio (2.8.1.12.) (Page 200) is set to the following:
B.10

Service Ratio Duty Backup

Relay function (2.8.1.4.) (Page 195) =
based on the number of hours each pump has run and the specified ratios that each pump
requires. Only one pump can run at a time.
This algorithm is the same as Service Ratio Duty Assist except that it will run only one pump
at a time. When the next pump in the sequence starts, the previous pump stops.
B.11

First In First Out

Relay function (2.8.1.4.) (Page 195) =
Alternate
in, first out
This algorithm starts pumps in the same way as Alternate Duty Assist but uses staggered
OFF setpoints to shut the pumps down. When the first OFF setpoint is reached, the FIFO
rule shuts down the first pump started. For example: pumps started in sequence 2, 3, 1
would be shut down in sequence 2, 3, 1.
318
Relay Index
1
2
3
duty, but uses staggered OFF setpoints and shuts down pumps based on the
rule.
Service Ratio Duty Assist selects the lead pump
Service Ratio Duty Backup selects the lead pump
First In First Out selects the lead pump based on the
Operating Instructions, 06/2018, A5E36281317-AC
Value
25
25
50
first
HydroRanger 200 HMI