Setting A Pump Up (Reservoir) Group - Siemens HydroRanger 200 HMI Operating Instructions Manual

Sitrans ultrasonic controllers
Hide thumbs Also See for HydroRanger 200 HMI:
Table of Contents

Advertisement

7.9.2

Setting a pump up (reservoir) group

Set a group of three pumps to pump up a reservoir.
Set the common parameters
Prerequisite: Substitute the details of your application in place of the sample values
provided. If you are bench testing the unit, set your test values to be the same as the sample
values.
Parameter
Sensor Mode (2.1.3.)
(Page 163)
Material (2.1.6.)
(Page 165)
Response Rate (2.3.4.)
(Page 174)
Transducer (2.1.5.)
(Page 164)
Units (2.1.1) (Page 162)
Empty (2.2.4.)
(Page 170)
Span (2.2.2.) (Page 169)
Example assumes a single measurement unit. If your device has dual-point software
1
installed, then some parameters are indexed by two level points.
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
Inflow
Span (2.2.2.) (Page 169)
Empty (2.2.4.) (Page 170)
Index
Transducer
Outflow
Value/Mode
1
Global
*Level (Page 163) Operation=*Level (Page 163)
Global
Liquid
Global
Medium
Global
XPS-10
Global
-
Global
1.8
Global
1.4
7.9 Pump control
Description
Material = *Liquid
Maximum Process Speed = *Medium
(1.0 m/min) (Page 174)
Transducer = XPS-10 (single-point
preset)
Units = Meters
Empty = 1.8 m
Span = 1.4 m
Operating
119

Advertisement

Table of Contents
loading

Table of Contents