Commissioning
6.3 Quick Start Wizards
End of QS Volume Wizard
For QS to be successful, all changes must be applied.
Options
To transfer Quick Start values to the device and return to Program menu, press DOWN
arrow
Note
It is strongly recommended that an Auto Zero Head be performed after completion of the
wizard to ensure best accuracy. See Auto Zero Head (2.15.2.) (Page 230).
6.3.1.4

Pump Control

Use this wizard to configure pumps if they will be used in your application. Be sure to first
complete the applicable Quick Start Wizard.
1. Press RIGHT arrow
MENU.
2. Press RIGHT arrow
3. Press RIGHT arrow
4. At each step, press DOWN arrow
next item, or RIGHT arrow
5. Scroll to desired item and press RIGHT arrow
arrow
6. At any time, you can press UP arrow
wizard.
Start of Wizard - Pump Control
Note
The introduction screen is displayed only on the device when using the local push buttons.
This screen is not part of the Quick Start when using SIMATIC PDM.
Shows the type of Wizard to be executed.
Options
74
BACK, CANCEL, FINISH
(Display returns to 1.1 Quick Start menu when Quick Start is successfully completed or
cancelled. If CANCEL is selected, no changes are written to the device.)
(Finish). Then press LEFT arrow
to activate PROGRAM mode and open menu level 1: MAIN
two times to navigate to menu item 1.1.
to open QS Level.
to continue.
CANCEL, START
three times to return to Measurement mode.
to accept default values and move directly to the
to open Edit mode: the current selection is highlighted.
to store the change, then press DOWN
to go back, or LEFT arrow
Operating Instructions, 07/2019, A5E33329501-AC
to cancel the
SITRANS LUT400