Parameter reference
8.6 Setup (2.)
Down sampling (2.11.5.3.)
Sets the number of consecutive echoes that must occur below the echo currently locked
onto before the measurements are validated as the new reading [for Echo Lock (2.11.5.4.)
(Page 235) = Maximum verification or Material agitator]
Index
Values
Related
Echo Lock (2.11.5.4.) (Page 235)
Maximum verification
Material agitator
Example setting:
● Echo Lock (2.11.5.4.) (Page 235) = Material agitator
● Up Sampling (2.11.5.2.) (Page 233) = 5
● Down sampling (2.11.5.3.) = 2
Result:
● Five consecutive measurements higher than the current reading will validate a new
reading.
OR
● Two consecutive measurements lower than the current reading will validate a new
reading.
Resetting Echo Lock (2.11.5.4.) (Page 235) returns Up Sampling (2.11.5.2) (Page 233) and
Down Sampling ( 2.11.5.3.) to their respective preset values.
234
Single-point model
Global
Range: 1 ... 50
Preset: 2
Echo lock (2.11.5.4.) (Page 235)
•
Up sampling (2.11.5.2.) (Page 233)
•
Dual-point model
Transducer
Up Sampling value
5
2
Operating Instructions, 06/2018, A5E36281317-AC
HydroRanger 200 HMI