Parameter reference
8.6 Setup (2.)
Exponent (2.10.2.3.)
Establishes the number of flow units required to increment the Flow Sampler (the device
connected to the relay set to Relay Function (2.8.1.4.) (Page 195) = Flow Sampler), in
conjunction with Mantissa (2.10.2.2.) (Page 213).
Index
Values
Related
This parameter is relevant only if Operation is set to OCM [Sensor Mode (2.1.3.) (Page 163)
= Flow rate in open channel].
Enter the exponent (Z) for the mantissa (Y) in the formula:
Flow Sampler Increment = Y x 10
214
Single-point model
Global
Range: -3 to +7 (integers only)
Preset: 0
Sensor mode (2.1.3.) (Page 163)
Relay function (2.8.1.4.) (Page 195)
Primary measuring device (2.13.2.) (Page 240)
Flow exponent (2.13.4.1) (Page 241)
PMD dimensions (2.13.5.) (Page 246)
Maximum head (2.13.4.2.) (Page 243)
Maximum flow (2.13.4.3.) (Page 243)
Zero head (2.13.4.5.) (Page 244)
Flow time units (2.13.4.4.) (Page 244)
Flowrate decimal (2.13.4.6.) (Page 245)
Head 1 (2.13.6.1.1.) (Page 247)
Flow 1 (2.13.6.1.2.) (Page 248)
Low flow cutoff (2.13.4.8.) (Page 246)
Auto zero head (2.13.3.) (Page 240)
Mantissa (2.10.2.2.) (Page 213)
Flow units