Operating
7.9 Pump control
7.9.4.8

Grouping pumps

You can group pumps and use the same pumping algorithm separately on each group. If you
specify different pumping algorithms, then you do not need to use this parameter because
the pumps are already grouped by algorithm.
Group pumps only when four pumps are using the same algorithm, and you want to split
them into two groups.
Example:
Pumps 1 and 2 will operate as a group, and Pumps 3 and 4 will operate as another group.
Parameter
Pump Group (2.8.2.2.)
(Page 201)
Pump Group (2.8.2.2.)
(Page 201)
Pump Group (2.8.2.2.)
(Page 201)
Pump Group (2.8.2.2.)
(Page 201)
7.9.4.9

Setting a flush valve

A flush valve stirs up the sediment at the bottom of the well during pumping, so that it doesn't
accumulate. These parameters will control any relays set with Relay Function (2.8.1.4.)
(Page 195) = Flush Valve. Most sets of parameters will work with only one or two changes;
however, for these parameters to work, all of them must be set to a value.
Example:
The flush valve connects to Relay 4 and the watched pump is on Relay 1.
Parameter
Relay Selector (2.10.3.1.)
(Page 216)
Flush Pump (2.10.3.2.)
(Page 216)
Flush Cycles (2.10.3.3.)
(Page 217)
Flush Interval (2.10.3.4.)
(Page 217)
Flush Duration (2.10.3.5.)
(Page 217)
130
Index
Mode
1
*Group 1 (Page 201)
2
*Group 1 (Page 201)
3
Group 2 (Page 201)
4
Group 2 (Page 201)
Index
Value
-
4
Global
1
Global
3
Global
10
Global
120
Description
Groups Pumps 1 and 2
Groups Pumps 3 and 4
Description
Flush valve is connected to Relay 4
Watch Relay 1 to count pump cycles
Open the flush valve for 3 cycles
Use the flush value every 10 cycles
Open the flush valve for 120 seconds
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC