Echo marker (2.11.2.9.)
The point on the primary echo on which the measured value is based.
Index
Values
Related
Use this feature if the reported material level fluctuates slightly, due to a variable rise in the
leading edge of the true echo on the Echo Profile.
Enter the value (in percent of echo height) to ensure the Echo Lock Window intersects the
Echo Profile at the sharpest rising portion of the Echo Profile representing the true echo.
Short shot bias (2.11.2.10.)
Slants the echo evaluation in favor of the short shot echo when both short and long shots are
evaluated [see Shot/pulse mode (2.1.17.) (Page 168).
Index
Values
Related
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
Single-point model
Global
Range: 5 ... 95%
Preset: 50%
Algorithm (2.11.2.2.) (Page 222)
Spike filter (2.11.2.7.) (Page 224)
Narrow echo filter (2.11.2.6.) (Page 224)
Reform echo (2.11.2.5.) (Page 223)
Single-point model
Global
Range: 0 ... 100
Preset: 20
Shot/pulse mode (2.1.17.) (Page 168)
Number of short shots (2.1.11.) (Page 166)
Short shot frequency (2.1.7.) (Page 165)
Long shot duration (2.1.10.) (Page 166)
Short shot floor (2.11.2.11.) (Page 226)
Short shot range (2.11.2.12.) (Page 226)