7.10.2

Setting common parameters

Prerequisite:
Substitute the details of your application in place of the sample values provided. If you are
bench testing the unit, set your test values to be the same as the sample values.
Parameter
Sensor mode (2.1.3.)
(Page 163)
Material (2.1.6.)
(Page 165)
Response rate (2.3.4.)
(Page 174)
Transducer (2.1.5.)
(Page 164)
Units (2.1.1.)
(Page 162)
Empty (2.2.4.)
(Page 170)
Span (2.2.2.)
(Page 169)
7.10.3

Set Relay 1 (Operate Rake)

Parameter
Level Source (2.8.1.2.)
(Page 194)
Relay Function (2.8.1.4.)
(Page 195)
ON Setpoint (2.8.1.5.)
(Page 197)
OFF Setpoint (2.8.1.6.)
(Page 197)
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
Index
Mode/Value
Global
Dual-point Difference
(Page 163)
Global
*Liquid (Page 165)
1 & 2
*Medium (1.0 m/min)
(Page 174)
1 & 2
XPS-10 (single-point pre-
set)
Global
1
1
1.8
2
2.2
1
1.4
2
1.4
3
1.4
Index
Mode/value
1
Difference or average
1
Fixed Duty Assist
1
0.4
1
0.1
Operating
7.10 Rake (screen) control
Description
Operation=Differential
Material=Liquid
Max. Process Speed=Medium
Transducer=XPS-10
Units=Meters
Empty=1.8 m
Empty=2.2 m
Span=1.4 m
Span=1.4 m
Max Differential=1.4 m
Description
Starts the rake when the
difference between the two
levels rises above 0.4 m and
stops the rake when the
difference falls below 0.1 m.
133