Level Application - Siemens HydroRanger 200 HMI Operating Instructions Manual

Sitrans ultrasonic controllers
Hide thumbs Also See for HydroRanger 200 HMI:
Table of Contents

Advertisement

Commissioning
6.7 Application examples
6.7.1

Level application

Quick Start parameter
Transducer
Operation
Temperature Source
Units
Empty
Span
Response Rate
See Fill rate/minute (2.3.2.) (Page 173)
1
The application is a vessel that takes an average 3 hours (180 minutes) to fill and 3 weeks to
empty.
Fill rate = (Empty – Span) / fastest of fill or empty time
= (15.5 m – 1 m) / 180 min.
= 14.5 m /180 min. = 0.08 m/min.
88
Space 7.5 m
1.0 m
Span
Distance 8.5 m
Sensor reference point
15.0 m
Empty
Range extension
Level 6.5 m
Setting
Description
XPS-15
Transducer to be used with the device
Level
Material level referenced from Low Cal. Point
TS-3
Temperature source
m
Sensor measurement units
15.0
Process empty level
1.0
Process full level
Slow
Sets Fill Rate
Operating Instructions, 06/2018, A5E36281317-AC
/ Empty Rate to 0.1 m/minute
1
HydroRanger 200 HMI