1
The device was designed to make it easy for master devices to get useful information via
Modbus. This chart gives an overview of the different sections. A more detailed explanation
of each section follows below.
C.11

Word order (R40,062)

This determines the format of unsigned, double-register integers (UINT32).
● 0 indicates that the most significant word (MSW) is given first
● 1 indicates that the least significant word (LSW) is given first
See Unsigned double precision integer (UINT32) (Page 340) for more information.
C.12

Map ID (R40,063)

This value identifies the register map used by the device. See Parameter Index Location
(4.11.) (Page 270) and Parameter access (R43,998-R46,999) (Page 333) for details.
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
Description
Start
Temperature (2)
41,030
Totalizer for Points
41,040
1 and 2
Discrete Inputs (2)
41,070
Relay Outputs (3 or
41,080
6)
mA Input (1)
41,090
mA Output (2)
41,110
Pump ON Setpoint
41,420
(3 or 6)
Pump OFF Setpoint
41,430
(3 or 6)
Pumped Volume (2) 41,440
Pump Hours (3 or 6) 41,450
Pump Starts (3 or 6) 41,470
43,998 ... 46,999
C.11 Word order (R40,062)
#R
Data type
1
2
–50 ... 150
4
UINT32
1
Bit Mapped
1
Bit Mapped
1
0000 ... 20,000 R
2
0000 ... 20,000 R/W
6
0000 ... 10,000 R/W
6
0000 ... 10,000 R/W
4
UINT32
12
UINT32
6
0000 ... 10,000 R
Communications
Read/write
R
R/W
R
R/W
R
R
R/W
329