Diagnosing and troubleshooting

10.4 Noise problems

Symptom
Displays Error and
tb:(#).
Displays EEEE
Reading fluctuates
while material level is
still (or vice versa).
Reading is fixed, re-
gardless of the actual
material level.
Material level reported
is always incorrect by
the same amount.
Measurement accuracy
improves as level nears
transducer.
Reading is erratic, with
little or no relation to
material level.
10.4
Noise problems
Incorrect readings can be the result of noise problems, either acoustic or electrical, in the
application. The noise present at the input to the ultrasonic receiver can be determined by
viewing the echo profile locally via the HMI, or alternatively, using remote software such
SIMATIC PDM. View also parameters Noise Average (3.2.11.5.) (Page 263) and Noise Peak
(3.2.11.6.) (Page 263). In general, the most useful value is the average noise.
With no transducer attached the noise is under 5 dB. This is often called the noise floor. If
the value with a transducer attached is greater than 5 dB, signal processing problems can
occur. High noise decreases the maximum distance that can be measured. The exact
relationship between noise and maximum distance is dependent on the transducer type and
the material being measured. An average noise level greater than 30 dB may be cause for
concern if the installed transducers maximum operation range matches the range of the
application (e.g. 8 m application using an 8 m XRS-5). Using a larger transducer with greater
transmitted energy should help to improve performance in a noise condition.
286
cause
Wrong transducer selected
Transducer selector
(2.1.4.) (Page 164).
Transducer connected in
"two-wire" method.
Transducer connected
backwards.
Value too large to display
in 4 or 5 characters.
Incorrect measurement
stabilization.
Transducer acoustic beam
obstructed, standpipe too
narrow, or transducer
ringing (reads over 100%).
Incorrect empty (zero)
reference for level opera-
tion [Sensor Mode (2.1.3.)
(Page 163) = *Level].
Incorrect Sound Velocity
used for distance calcula-
tion.
True echo too weak or
wrong echo being pro-
cessed.
Action
Verify transducer type and re-enter value.
Do not tie white and shield together. Use all
three terminal blocks.
Reverse black and white wires on terminal
block.
Select larger units [ Units (2.1.1.) (Page 162)],
or lower convert reading [Convert reading
(2.12.5.) (Page 238)].
Alter rate of response [Response rate (2.3.4.)
(Page 174)] or rate filter [Rate filter (2.3.5.)
(Page 175)] accordingly.
Relocate and / or re-aim transducer at materi-
al level or object.
Proceed to Measurement difficulties
(Page 289).
See Empty (2.2.4.) (Page 170), Offset reading
(2.12.6.) (Page 238), Sensor offset (2.2.5.)
(Page 171), Offset correction (2.11.1.9.)
(Page 221)
Use a transducer with a built-in temperature
sensor or a TS-3 temperature sensor.
See Sound velocity (2.11.1.2.) (Page 218).
Relocate and/or re-aim transducer at material.
Check noise parameters. See Noise problems
(Page 286).