7.9.4.3

Totalizing pumped volume

Prerequisite: The volume of the vessel must be known.
Parameter
Sensor Mode (2.1.3.)
(Page 163)
Material (2.1.6.) (Page 165) Global
Response Rate (2.3.4.)
(Page 174)
Transducer (2.1.5.)
(Page 164)
Units (2.1.1.) (Page 162)
Empty (2.2.4.) (Page 170)
Span (2.2.2.) (Page 169)
Vessel Shape (2.7.2.)
(Page 186)
Maximum Volume (2.7.3.)
(Page 188)
Relay Function (2.8.1.4.)
(Page 195)
Relay Function (2.8.1.4.)
(Page 195)
Relay Function (2.8.1.4.)
(Page 195)
ON Setpoint (2.8.1.5.)
(Page 197)
ON Setpoint (2.8.1.5.)
(Page 197)
ON Setpoint (2.8.1.5.)
(Page 197)
OFF Setpoint (2.8.1.6.)
(Page 197)
OFF Setpoint (2.8.1.6.)
(Page 197)
OFF Setpoint (2.8.1.6.)
(Page 197)
Set in RUN Mode
1. Press the LEFT arrow
2. Once there, press the DOWN arrow
3. Press the LEFT arrow
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
Index
Mode/Value
Global
Pump Totalizer
*Liquid
Global
*Medium (1.0 m/ min)
Global
XPS-10 (singlepoint
preset)
Global
Meters
Global
1.8
Global
1.4
Global
Flat Level Bottom
Global
17.6
1
Alternate Duty Assist
2
Alternate Duty Assist
3
Alternate Duty Assist
1
1.0
2
1.2
3
1.4
1
0.2
2
0.2
3
0.2
to go to Measurement View mode.
to show Measurement View 2.
until Totalizer is shown.
Operating
7.9 Pump control
Description
Operation = Pumped volume
These parameters are as
shown above.
Tank shape is Flat Level Bot-
tom.
Max volume is 17.6 m
or
3
17,600 liters.
Sets Relays 1, 2, and 3 as a
pump group using Alternate
Duty Assist.
Sets the ON setpoints for the
pump group.
Sets the OFF setpoints for the
pump group.
127