Echo Select (2.11.2.) - Siemens HydroRanger 200 HMI Operating Instructions Manual

Sitrans ultrasonic controllers
Hide thumbs Also See for HydroRanger 200 HMI:
Table of Contents

Advertisement

Parameter reference
8.6 Setup (2.)
8.6.11.2

Echo Select (2.11.2.)

Transducer selector (2.11.2.1.)
Sets the transducer index for all parameters applicable to this sub-menu.
Algorithm (2.11.2.2.)
Selects the algorithm to generate the measured value from the profile.
Index
Options
Related
Use this to select the algorithm(s) the Sonic Intelligence echo selection is based on. Use
Long Confidence (3.2.11.2.) (Page 262) to determine which algorithm gives the highest
confidence under all level conditions. If the wrong echo is processed, observe the echo
processing displays and select an alternate algorithm using this parameter.
For details on echo determinations and suggested usage, see Algorithm (Page 304).
222
Single-point model
Global
ALF Area Largest First
A Echo Area
L Largest Echo
F First Echo
AL Area Largest
AF Area First
LF Largest First
*BLF Best F-L
BL Best L
BF Best F
TF True First Echo
Reform echo (2.11.2.5.) (Page 223)
Narrow echo filter (2.11.2.6.) (Page 224)
Spike filter (2.11.2.7.) (Page 224)
Echo marker (2.11.2.9.) (Page 225)
Long confidence (3.2.11.2.) (Page 262)
Dual-point model
Transducer
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC