Parameter reference
8.6 Setup (2.)
8.6.4.9

mA Fail-safe value (2.4.9.)

Sets the mA value to be reported when the fail-safe timer expires.
Note
Fail-safe mode (2.4.4.) (Page 178) must be set to Value in order for the Material Level value
to be reported.
Index
Values
8.6.5

Current Output (2.5.)

Sets the parameters applicable to the current value of the mA output.
8.6.5.1

mA output selector (2.5.1.)

Sets the mA output index for all parameter settings.
Options
8.6.5.2

mA output range (2.5.2.)

Determines the mA output range.
Index
Options
Related
If either 0 to 20 mA or 4 to 20 mA is selected, the mA output is directly proportional to the mA
Function. If either 20 to 0 mA or 20 to 4 mA is selected, then the output is inversely
proportional. After setting mA output range (2.5.2.), verify that Minimum mA limit (2.5.7.)
(Page 182) has a valid entry, as it is not changed automatically by setting the mA output
range (2.5.2.).
180
mA Output
Range: 0 ... 22 mA
Preset: 3.58 mA
*mA Output 1
mA Output 2
mA Output
OFF
0 ... 20 mA
*4 ... 20 mA
20 ... 0 mA
20 ... 4 mA
Milliamp output (2.5.9.) (Page 182)
HydroRanger 200 HMI