8.6.3.5

Rate filter (2.3.5.)

Damps the Flow Maximum (3.2.8.15.) (Page 259) fluctuations
Index
Options
Alters
Altered by
Related
Enter the time or distance interval over which the Flow Maximum (3.2.8.15.) (Page 259) is to
be calculated before the display updates.
This is automatically altered along with Response Rate (2.3.4.) (Page 174).
This value automatically alters the Rate Filter Time (2.3.6.) (Page 175) and/or Rate Filter
Distance (2.3.7.) (Page 175). Alternatively, these parameter values may be altered
independently.
8.6.3.6

Rate filter time (2.3.6.)

The time period, in seconds, over which the material level rate of change is averaged before
Flow Maximum (3.2.8.15.) (Page 259) updates.
Index
Values
Related
8.6.3.7

Rate filter distance (2.3.7.)

The material level change, in meters, to initiate a Flow Maximum (3.2.8.15.) (Page 259)
update.
Index
Values
Related
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
Single-point model
Global
Rate display not required
Filtered Output: Continuous filtering and update
Interval Output:
*1 min or 50 mm (2 in)
5 min or 100 mm (3.9 in)
10 min or 300 mm (11.8 in)
10 min or 1000 mm (39.4 in)
Flow Maximum (3.2.8.15.) (Page 259)
Response Rate (2.3.4.) (Page 174)
Rate Filter Time (2.3.6.) (Page 175)
Rate Filter Distance (2.3.7.) (Page 175)
Single-point model
Global
Range: 0.000 ... 9999 seconds
Flow Maximum (3.2.8.15.) (Page 259)
Single-point model
Global
Range: 0.000 ... 9999 meters
Flow Maximum (3.2.8.15.) (Page 259)
Parameter reference
Dual-point model
Transducer
Dual-point model
Transducer
Dual-point model
Transducer