8.6.13.5

PMD dimensions (2.13.5.)

Sets the dimensions of the Primary Measuring Device (PMD).
Use this parameter if the Primary Measuring Device (2.13.2.) (Page 240) is directly
supported. The dimensions required for each PMD vary.
The following table is a reference to the parameters that must be set for each PMD.
Index
Index values for
supported PMDs
PMD selected
Altered by
246
Single-point model
Global
Range: 0.000 ... 9999
Preset: 5.000 %, in equivalent units
Units (2.1.1.) (Page 162)
Span (2.2.2.) (Page 169)
Single-point model
Global
Dimension name (parameter menu reference)
Thin Plate V-Notch Weir
Notch angle [OCM Dimension 1 (2.13.5.1.)]
Discharge coefficient [OCM Dimension 2 (2.13.5.2.)], Read only
Rectangular Flume BS-3680/ISO 4359
Approach width B [OCM Dimension 1 (2.13.5.1.)]
Throat width b [OCM Dimension 2 (2.13.5.2.)]
Hump height P [OCM Dimension 3 (2.13.5.3.)]
Throat Length L [OCM Dimension 4 (2.13.5.4.)]
Velocity coefficient [OCM Dimension 5 (2.13.5.5.)], Read only
Discharge coefficient [OCM Dimension 6 (2.13.5.6.)], Read only.
Cross sectional area [OCM Dimension 7 (2.13.5.7.)], Read only.
Palmer-Bowlus
Flume width [OCM Dimension 1 (2.13.5.1.)]
H-Flume
Flume height [OCM Dimension 1 (2.13.5.1.)]