Siemens HydroRanger 200 HMI Operating Instructions Manual page 247

Sitrans ultrasonic controllers
Hide thumbs Also See for HydroRanger 200 HMI:
Table of Contents

Advertisement

Flowrate decimal (2.13.4.6.)
Sets the maximum number of decimal places to be displayed in the auxiliary reading.
Index
Options
Altered by
The maximum number of decimal places shown in the Primary Reading is controlled by
Decimal Position (2.12.4.) (Page 237).
Flowrate units (2.13.4.7.)
Defines the units used for flow calculations.
Note
Set this parameter only when using BS-3680/ISO 4359 Rectangular Flume or BS-3680/ISO
1438/1 Thin Plate V-Notch Weir [Primary Measuring Device (2.13.2.) (Page 240) =
Rectangular Flume BS-36806 or Thin Plate V-Notch Weir BS-36807]. Use the default option
of Ratiometric calculation for Flowrate Units (2.13.4.7.) when Primary Measuring Device
(2.13.2.) (Page 240) = Exponential devices, Palmer-Bowlus Flume, H-Flume, Universal
Linear Flow Calculation, or Universal Curved Flow Calculation.
Index
Options
Alters
Altered by
Related
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
Single-point model
Global
No digits
1 digit
*2 digits
3 digits
Decimal position (2.12.4.) (Page 237)
Single-point model
Global
Ratiometric
[Primary Measuring Device (2.13.2.)
(Page 240) = all]
Absolute
[Primary Measuring Device (2.13.2.)
(Page 240) = Rectangular Flume BS-
3680 or Thin Plate VNotch Weir BS-
3680 only]
Flow time units (2.13.4.4.) (Page 244)
Primary measuring device (2.13.2.) (Page 240)
Flowrate decimal (2.13.4.6.) (Page 245)
Parameter reference
Dual-point model
Transducer
Dual-point model
Transducer
*Ratiometric calculation
L/S (Liters/second)
M
/H (Cubic meters/hour)
3
M
/D (Cubic meters/day)
3
FT
/S (Cubic feet/second)
3
IMPGAL/MIN (Gallons/minute – Imperi-
al)
MIMPGAL/D (Million gallons/day –
Imperial)
GAL/MIN (Gallons/minute – U.S.)
MUSGAL/D (Million gallons/day – U.S.)
8.6 Setup (2.)
245