Sensor Offset (2.2.5.); Blanking (2.2.6.) - Siemens HydroRanger 200 HMI Operating Instructions Manual

Sitrans ultrasonic controllers
Hide thumbs Also See for HydroRanger 200 HMI:
Table of Contents

Advertisement

8.6.2.5

Sensor offset (2.2.5.)

Calibrates Empty (2.2.4.) (Page 170) if the reported level is consistently high or low by a
fixed amount.
Index
Values
Related
Before using this feature, verify the following parameters are correct:
● Empty (2.2.4.) (Page 170)
● Process temperature (2.11.1.3.) (Page 218)
● Offset reading (2.12.6.) (Page 238) (if using OCM)
● Zero head (2.13.4.5.) (Page 244)
Offset calibration
Begin with a steady level.
1. Measure the actual reading (use tape measure).
2. Enter the measured value from Step 1 into this parameter.
The deviation between the entered Empty (2.2.4) (Page 170) value and the calibrated Empty
value is stored in Offset Correction (2.11.1.9.) (Page 221)
8.6.2.6

Blanking (2.2.6.)

The space near the transducer face which cannot be measured.
Index
Values
Related
Use this feature if the surface is reported to be near the transducer face but is in fact much
further away. Extend this value when changing transducer location, mounting, or aiming.
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
Single-point model
Global
Range: -999 ... 9999
Empty (2.2.4.) (Page 170)
Offset reading (2.12.6.) (Page 238)
Zero head (2.13.4.5.) (Page 244)
Offset correction (2.11.1.9.) (Page 221)
Process temperature (2.11.1.3.) (Page 218)
Single-point model
Global
Range: Range: 0.000 ... 99.00 m or equivalent, depending on Units (2.1.1.)
(Page 162)
Preset
0.300 m (most transducers)
0.450 m (XCT-8, XCT-12)
Empty (2.2.4.) (Page 170)
Span (2.2.2.) (Page 169)
TVT dB (2.11.3.7.) (Page 230)
Parameter reference
Dual-point model
Transducer
Dual-point model
Transducer
8.6 Setup (2.)
171

Advertisement

Table of Contents
loading

Table of Contents