Relay controlled by communications

A relay can be controlled directly by a remote system through communications. No other
control schemes can then be used with a relay configured this way. Communications can be
used to force status of some control relays, such as pumps.
Settings
Parameter
Relay Function (2.8.1.4.)
(Page 195)
7.9.4.11

Tracking pump usage

You can find out how much an individual pump has been used by viewing the pump records
parameters.
Information available
Current RUN time
Total pump hours
Total pump starts
Total pump RUN on occurrences
7.10

Rake (screen) control

Rakes or screens are mounted on the inflow channel of the wastewater treatment plant to
prevent debris from clogging the equipment. When material builds up on the screen, a level
differential is created, and the water level is higher in front of the screen than behind it. When
this differential reaches the programmed setpoint, the device activates a relay to operate
mechanical rakes that clean the screen and ensure a steady flow.
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
Index
Mode
5
Communication
Parameter access
Pump Run Time (3.2.9.3.) (Page 260)
Pump Hours (3.2.9.2.) (Page 260)
Pump Starts (3.2.9.4.) (Page 260)
Pump Run-ONs (3.2.9.5.) (Page 260)
7.10 Rake (screen) control
Description
Sets Relay 5 to communications con-
trol
Operating
131