Siemens SITRANS LUT400 Operating Instructions Manual

Siemens SITRANS LUT400 Operating Instructions Manual

Ultrasonic controllers
Hide thumbs Also See for SITRANS LUT400:
Table of Contents

Advertisement

Quick Links

Operating instructions
SITRANS
Ultrasonic controllers
SITRANS LUT400
Edition
07/2019
www.siemens.com/processautomation

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SITRANS LUT400

  • Page 1 Operating instructions SITRANS Ultrasonic controllers SITRANS LUT400 Edition 07/2019 www.siemens.com/processautomation...
  • Page 3 Ultrasonic level transmitters SITRANS LUT400 Connecting Commissioning Operating Instructions General Operation Remote Operation Parameter reference (LUI) Service and Maintenance Diagnosing and Troubleshooting Technical data Dimension drawings Technical reference 7ML5400 (SITRANS LUT400) Technical Support List of abbreviations 07/2019 LCD menu structure A5E33329501-AC...
  • Page 4 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 5: Table Of Contents

    Preparation for cable entry ..................... 29 4.2.4.1 Cable routed through conduit ....................29 4.2.4.2 Cable exposed and entering through the cable glands ............30 SITRANS LUT400 wiring compartment .................. 31 The Battery ..........................31 Connecting .............................. 32 Connecting SITRANS LUT400 ....................34 5.1.1 Wiring compartment ........................
  • Page 6 Remote mounted lid with extension cable ................46 5.1.11 Extension cable ........................48 Connecting in hazardous area installations ................49 Commissioning ............................50 Local Commissioning ......................50 Activating SITRANS LUT400 ....................51 6.2.1 The LCD Display ........................52 6.2.1.1 Measurement mode display: Normal operation ..............52 6.2.1.2 PROGRAM mode display ......................
  • Page 7 Set Relays to FIXED DUTY ASSIST (FDA) ................. 107 7.7.3.3 Set Relays to FIXED DUTY BACKUP (FDB) ............... 107 7.7.3.4 Set Relays to SERVICE RATIO DUTY ASSIST (SRA) ............108 7.7.3.5 Set Relays to SERVICE RATIO DUTY BACKUP (SRB) ............109 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 8 HART status ......................... 155 7.14.4 Simulation process ....................... 155 7.14.4.1 Simulating a fixed level ......................156 Simulating a changing level ....................156 7.14.4.2 7.14.4.3 Simulating Discrete Inputs ....................156 7.14.4.4 Simulation timeout ....................... 157 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 9 Table of contents 7.14.5 Application test ........................157 7.15 SITRANS LUT400 Communication Systems ............... 158 7.15.1 LUT400 Communications (HART) ..................158 7.15.1.1 HART Version ........................158 7.15.1.2 Burst mode ..........................158 7.15.1.3 HART multi-drop mode ......................159 7.15.1.4 SIMATIC PDM ........................159 7.15.1.5...
  • Page 10 Fail-safe Fault Alarm (2.8.8.) ....................203 9.2.8.9 High Flowrate Alarm (2.8.9.) ....................204 9.2.8.10 Low Flowrate Alarm (2.8.10.) ....................205 9.2.8.11 Relay Logic (2.8.11.) ......................206 9.2.8.12 Time To Spill (2.8.12.) ......................207 9.2.9 Discrete Inputs (2.9.) ......................207 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 11 9.3.1.6 Product (3.1.6.) ........................240 9.3.1.7 Order No. (Order Number in PDM) (3.1.7.) ................240 9.3.1.8 Serial Number (3.1.8.) ......................240 9.3.1.9 Final Assembly Number (3.1.9.) ................... 240 9.3.1.10 Hardware Revision (3.1.10.) ....................240 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 12 Diagnosing and Troubleshooting ......................267 11.1 Communication Troubleshooting ..................267 11.1.1 Generally ..........................267 11.1.2 Specifically ........................... 267 11.2 Device Status Icons ......................268 11.3 General Fault Codes ......................269 11.4 Common Problems Chart ....................273 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 13 Obstructions in the Sound Beam ..................280 11.7.2 Nozzle Mountings ......................... 281 11.7.3 Set the SITRANS LUT400 to Ignore the Bad Echo .............. 281 11.7.3.1 If the Echo is Close to the Transducer.................. 281 11.7.3.2 Adjust the TVT to Ignore the Echo ..................281 11.8...
  • Page 14 Method of Flow Calculation ....................302 A.7.2 Data Logging ........................303 Technical Support ..........................305 Technical support ......................... 305 Certificates ........................... 305 List of abbreviations ..........................306 LCD menu structure ..........................308 Glossary ..............................320 Index ..............................323 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 15: Introduction

    Introduction The Manual This manual will help you set up your SITRANS LUT400 for optimum performance. For other Siemens level measurement manuals, go to: www.siemens.com/level (www.siemens.com/level), and look under Level Measurement. Note • This product is intended for use in industrial areas. Operation of this equipment in a residential area may cause interference to several frequency-based communications.
  • Page 16: Application Examples

    • Correction of flow rate on exponential devices using absolute calculation. 1.01.01 February 1, 2014 Added Russian, Portuguese and Italian language support. 1.02.00 December 1, 2014 Added user changeable password and First In, First Out data- log option. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 17: Security Information

    Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure...
  • Page 18: Safety Notes

    Dispose of in an environmentally safe manner, and according to local regulations. WARNING: refer to accompanying documents (manual) for details. CAUTION: Observe electrostatic discharge precautions prior to handling electronic components within the wiring compartment. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 19: Fcc Conformity

    US Installations only: Federal Communications Commission (FCC) rules Note Void user authority Changes or modifications not expressly approved by Siemens could void the user’s authority to operate the equipment. Note This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules.
  • Page 20 CO concentrations), should be properly assessed to ensure safe reliable use in the event of measurement errors due to sound wave velocity changes. Please contact your local Siemens representative for assistance. SITRANS LUT400...
  • Page 21: Description

    Transducers, allowing an ® operating range of 0.3 to 60 meters (dependent on transducer). The SITRANS LUT400 has been coupled with a backlit Local User Interface (LUI) display featuring menu driven programming and a host of wizards for plug and play performance. The LUT400 also...
  • Page 22: Models

    Description 3.2 Models Models The SITRANS LUT400 comes in three different models, depending on the application, level of performance and functionality required: ● SITRANS LUT420 Level Controller - Level or volume measurement, basic pump control functions, and basic data logging capability ●...
  • Page 23: Installing And Mounting

    Mounting locations ● Ambient temperature is always within -20 to +50 °C (-4 to +122 °F). ● SITRANS LUT400 display window is at shoulder level, unless most interaction is through a SCADA system. ● Easy access to local push buttons is provided.
  • Page 24: Mounting Instructions

    All configurations of the SITRANS LUT400 are shipped with a mounting back plate. SITRANS LUT400 has the option of a lid with a Local User Interface (LUI) display, a remote display for panel mount configuration, or a blank lid. The panel mount model comes with both a LUI display and a blank lid.
  • Page 25 Wall mount fasteners not included. ① Slotted features For a more detailed dimension drawing, see SITRANS LUT400 Dimensions (Page 288). 1. Mark and drill four holes in the mounting surface for the four screws (customer supplied). 2. Fasten with a screwdriver.
  • Page 26: Remote Mounted Lid

    Four panel mount fasteners provided ② Remote display lid ③ Gasket ④ Extension cable For a more detailed dimension drawing, see SITRANS LUT400 Dimensions (Page 288) and Cutout Dimensions (for Remote Panel Mount) (Page 289). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 27: Mounting The Remote Lid

    MUST be able to support four times the weight of the device. • Fasteners included: M5 screw, seal washer, M5 flat washer and nut. These fasteners are required to maintain IP65 rating on remote lid. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 28: Pipe Mount

    ⑤ Pipe Note Pipe mount fasteners not included. For a more detailed dimension drawing, see SITRANS LUT400 Dimensions (Page 288) and Cutout Dimensions (for Remote Panel Mount) (Page 289). 4.2.2.1 Mounting the enclosure 1. Fasten the mounting back plate to the pipe using u-bolts, saddle clamps, (customer supplied) suitable to pipe diameter.
  • Page 29 Maximum : 3" pipe size with M8 or 3/8" thread. Minimum: 3/4" pipe size with M6 or 1/4" thread. – Hex Nuts: M6 or 1/4" to M8 or 3/8". – Washer: Maximum: 16 mm or 13/16" outside diameter. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 30: Din-Rail Mount

    Installing and Mounting 4.2 Mounting instructions 4.2.3 DIN-rail mount ① DIN-rail ② Back of enclosure ③ Clips (2) ④ DIN-rail slide ⑤ Slot For a more detailed dimension drawing, see SITRANS LUT400 Dimensions (Page 288). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 31: Mounting The Enclosure

    Note Recommended mounting: directly to horizontal DIN-rail. Required DIN-rail dimensions: TH 35-7.5 or TH 35-15 per standard IEC 60715. The DIN-rail MUST be able to support four times the weight of the SITRANS LUT400. 4.2.3.2 Removing the enclosure 1. From the front of the device, place screwdriver in slot at bottom of DIN-rail slide and pry downward.
  • Page 32: Cable Exposed And Entering Through The Cable Glands

    Cable entry holes ③ Groove for screwdriver (3 places) For a more detailed dimension drawing, see SITRANS LUT400 Dimensions (Page 288). 4.2.4.2 Cable exposed and entering through the cable glands 6. After preparing for cable entry in steps 1 to 5 above, unscrew the glands and attach them firmly to the enclosure.
  • Page 33: Sitrans Lut400 Wiring Compartment

    Display cable The Battery The SITRANS LUT400 is supplied with one battery installed. The battery (BR2032) has a life expectancy of ten years, and is affected by ambient temperature. If the LUT400 loses input power, the battery will maintain operation of the device’s real time clock until power has been restored.
  • Page 34: Connecting

    ). To avoid differential ground potentials ensure cable shields are properly connected to ground. ● Keep exposed conductors on shielded cables as short as possible to reduce noise on the line caused by stray transmissions and noise pickup. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 35 Connecting ① Siemens Transducer ② Siemens TS-3 Temperature Sensor ③ HART FC375/475 or a computer running SIMATIC PDM, AMS Device Manager, FDT, or a web browser ④ Customer Alarm, Pump, or Control Device ⑤ Customer Device with Digital Output ⑥...
  • Page 36: Connecting Sitrans Lut400

    Connecting 5.1 Connecting SITRANS LUT400 Connecting SITRANS LUT400 CAUTION • Check the device label on your instrument, to verify the approval rating. • Use appropriate conduit seals to maintain IP or NEMA rating. Note Separate cables and conduits may be required to conform to standard instrumentation wiring practices or electrical codes.
  • Page 37: Wiring Compartment

    61010-1. • All field wiring must have insulation ratings suitable for the application. • Before applying power to the SITRANS LUT400 for the first time, ensure any connected alarm/control equipment is disabled until satisfactory system operation and performance is verified.
  • Page 38 Connecting 5.1 Connecting SITRANS LUT400 ① Ground ② L2/N ③ ④ Cable gland (or NPT cable entry) The SITRANS LUT400 is available in AC or DC power models. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 39 Connecting 5.1 Connecting SITRANS LUT400 AC: 100-230 V AC 15%, 50/60 Hz, 36 VA (10W) DC: 10-32 V DC, 10W Note Make sure device is connected to a reliable ground. 1. To wire for power, strip the cable jacket for approximately 70 mm (2.75") from the end of the cable, and thread the wires through the gland 2.
  • Page 40: Cables

    Preferred shielding is braided shield. WARNING Coaxial transducer cable extension Do not use a coaxial transducer cable extension with the SITRANS LUT400. High voltage transmitted on shield of coaxial cable could result in personal injury, damage to equipment, or poor device performance.
  • Page 41: Temperature Sensor

    5.1 Connecting SITRANS LUT400 Note The SITRANS LUT400 supports several different transducers. Some, like the XPS-30, are driven by a low power level, while others, like the XPS-15, are driven by a high power level. It may be possible to damage a lower power transducer like the XPS-30 if the transducer selection is currently set to one of the high power transducers.
  • Page 42: Relays

    Connecting 5.1 Connecting SITRANS LUT400 To achieve the best performance of temperature measurement in a typical open channel flow application, the temperature sensor should be shielded from direct sunlight and mounted half way between the ultrasonic transducer face and the maximum head achievable in the application.
  • Page 43: Communications

    Connecting 5.1 Connecting SITRANS LUT400 5.1.7 Communications The USB port and the 4 to 20 mA HART terminal block (terminal numbers 22, 23, and 24) are located inside the enclosure of the device. ① To Transducer ② To other SIEMENS unit ③...
  • Page 44 Connecting 5.1 Connecting SITRANS LUT400 USB connection ① USB cable Use 5-pin USB Mini-B cable. The cable should not exceed 3 m (9.8 ft.). Note Do not use a USB extension cable with the LUT400. Data Logging may not occur, even after extension cable has been disconnected.
  • Page 45: Connecting Hart

    Connecting 5.1 Connecting SITRANS LUT400 5.1.7.2 Connecting HART Typical PLC/mA configuration with Passive HART connection ① DC power supply (18-30V) ② ③ HART modem ④ HART communicator Typical PLC/mA configuration with Active HART connection ① ② HART modem ③ HART communicator...
  • Page 46: Level System Synchronization

    5.1.8 Level system synchronization Note The SITRANS LUT400 CANNOT be synchronized with the MultiRanger Plus, the original HydroRanger, or the OCMIII. When transducer cables are run parallel with each other, synchronize the level monitors so that no device transmits while another is waiting for echo reception. If more than one ultrasonic device is being installed in the same application, the devices must be synchronized to prevent cross-talk.
  • Page 47: Discrete Inputs

    For more information or assistance, contact Siemens or your local distributor. Go to: www.siemens.com/processautomation (www.siemens.com/processautomation). 5.1.9 Discrete inputs The SITRANS LUT400 has a 24V power bias (terminal 10) for use with the discrete inputs, or the discrete inputs can be wired using external power. ① Common Neg. for DIs ②...
  • Page 48: Remote Mounted Lid With Extension Cable

    Connecting 5.1 Connecting SITRANS LUT400 Note Terminals 6 and 7 must be connected together. Discrete Inputs used with external bias voltage 5.1.10 Remote mounted lid with extension cable The optional display lid can be mounted remotely up to 5 m from the device. The optional extension cable can be used for such an installation.
  • Page 49 Connecting 5.1 Connecting SITRANS LUT400 3. Separate from the device, knock out cable entry tab on blank lid: a. With gasket in place, use snips to cut into lid on both sides of the cable entry knockout. Use cutting guideline to cut from bottom of lid, up to bottom of groove (as shown below).
  • Page 50: Extension Cable

    Connecting 5.1 Connecting SITRANS LUT400 6. Connect extension cable to display cable on remote lid. 7. Secure blank lid on device and mount display lid remotely. See Remote mounted lid (Page 24). ① Blank lid ② Display cable connector ③...
  • Page 51: Connecting In Hazardous Area Installations

    In all cases, check the device label on your instrument, and confirm the approval rating. 1. Non-incendive wiring (Canada) CSA Class I, Div 2 connection drawing number A5E03936871 can be downloaded from the product page of our website at www.siemens.com/sitransLUT400 (www.siemens.com/sitransLUT400). SITRANS LUT400...
  • Page 52: Commissioning

    Local Commissioning Local Commissioning SITRANS LUT400 is an easy to use, and quick to commission device, with its numerous wizards, and menu driven parameters. The parameters can be modified locally using the LCD and the local push buttons, also known as the Local User Interface (LUI).
  • Page 53: Activating Sitrans Lut400

    (It will not return to the screen from which the timeout occurred.). 1. Power up the device. SITRANS LUT400 automatically starts up in Measurement mode. A transition screen showing first the Siemens logo and then the current firmware revision of the LUI is displayed while the first measurement is being processed.
  • Page 54: The Lcd Display

    Commissioning 6.2 Activating SITRANS LUT400 6.2.1 The LCD Display 6.2.1.1 Measurement mode display: Normal operation Level ① ② Measured value (level, space, distance, volume, flow, or head) ③ Value being displayed [Primary Variable (PV)=1 of 2, Secondary Variable (SV)=2 of 2] ④...
  • Page 55: Program Mode Display

    Commissioning 6.2 Activating SITRANS LUT400 Fault present ⑧ Text area displays a fault code and an error message ⑨ Service required icon appears 6.2.1.2 PROGRAM mode display ● A visible menu bar indicates the menu list is too long to display all items.
  • Page 56: Key Functions In Measurement Mode

    Commissioning 6.2 Activating SITRANS LUT400 6.2.1.3 Key functions in Measurement mode Function Result RIGHT arrow opens PROGRAM mode. Opens the top level menu. UP or DOWN arrow toggles between PV and LCD displays primary or secondary value. 6.2.2 Programming SITRANS LUT400 Note •...
  • Page 57 Commissioning 6.2 Activating SITRANS LUT400 PROGRAM Enter PROGRAM mode Using local push buttons: ● RIGHT arrow activates PROGRAM mode and opens menu level 1. Navigating: key functions in Navigation view Note • In Navigation view, ARROW keys move to the next menu item in the direction of the arrow.
  • Page 58 Commissioning 6.2 Activating SITRANS LUT400 Editing in PROGRAM mode Selecting a listed option ① Parameter name ② Menu name ③ Parameter number ④ Current value 1. Navigate to the desired parameter. 2. Press RIGHT arrow to open Edit mode. The current selection is highlighted.
  • Page 59: Quick Start Wizards

    A Wizard provides an easy step-by-step Quick Start (QS) procedure that configures the device for a simple application. To configure the SITRANS LUT400 for applications of level, volume (standard vessel shapes), or flow, use the Quick Start Wizards via LUI (Page 58) of this chapter.
  • Page 60: Quick Start Wizards Via Lui

    Parameter Configuration Charts that list all parameters and available options for each application type are available on our website. Go to www.siemens.com/sitransLUT400 (www.siemens.com/sitransLUT400) > Support > Application Guides. You can record data and select from options on the chart that apply to your application, then with this data on hand, complete the Quick Start Wizards via LUI (Page 58) below, or via another Quick Start Wizard, as referenced above.
  • Page 61: Quick Start

    5. Scroll to desired item and press RIGHT arrow to store the change, then press DOWN arrow to continue. 6. At any time, you can press UP arrow to go back, or LEFT arrow to cancel the wizard. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 62 This screen is not part of the Quick Start when using SIMATIC PDM. Shows the type of Wizard to be executed. Options CANCEL, START Transducer Specifies the Siemens transducer connected to the device. Options NO TRANSDUCER, XRS-5, XPS-10, XPS-15, XCT-8, XCT-12, XPS-30, XPS-40, XLT-30, XLT-60, STH Default: NO TRANSDUCER...
  • Page 63 This parameter is only displayed if FIXED TEMPERATURE selected for Temperature Source. Units Sensor measurement units. Options m, cm, mm, ft, in Default: m Note For the purpose of this example, all values are assumed to be in meters (m). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 64 If CANCEL is selected, no changes are written to the device.) To transfer Quick Start values to the device and return to Program menu, press DOWN arrow (Finish). Then press LEFT arrow three times to return to Measurement mode. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 65: Qs Volume

    5. Scroll to desired item and press RIGHT arrow to store the change, then press DOWN arrow to continue. 6. At any time, you can press UP arrow to go back, or LEFT arrow to cancel the wizard. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 66 This screen is not part of the Quick Start when using SIMATIC PDM. Shows the type of Wizard to be executed. Options CANCEL, START Transducer Specifies the Siemens transducer connected to the device. Options NO TRANSDUCER, XRS-5, XPS-10, XPS-15, XCT-8, XCT-12, XPS-30, XPS-40, XLT-30, XLT-60, STH Default: NO TRANSDUCER Temperature Source Source of the temperature reading used to adjust the speed of sound.
  • Page 67 6.3 Quick Start Wizards Vessel Shape Defines the vessel shape and allows the SITRANS LUT400 to calculate volume instead of level. If NONE is selected, no volume conversion is performed. Select the vessel shape matching the monitored vessel or reservoir.
  • Page 68 Determines volume measurement units. Value L, USGAL, IMPGAL, CUM, USER DEFINED * Default: L * If USER DEFINED option selected, the value must be set after completing the wizard. See User Defined Unit (2.6.6.) (Page 182). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 69: Qs Flow

    QS Flow. 4. At each step, press DOWN arrow to accept default values and move directly to the next item, or RIGHT arrow to open Edit mode: the current selection is highlighted. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 70 Start of QS Flow Wizard Note The introduction screen is displayed only on the device when using the local push buttons. This screen is not part of the Quick Start when using SIMATIC PDM. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 71 6.3 Quick Start Wizards Shows the type of Wizard to be executed. Options CANCEL, START Transducer Specifies the Siemens transducer connected to the device. Options NO TRANSDUCER, XRS-5, XPS-10, XPS-15, XCT-8, XCT-12, XPS-30, XPS-40, XLT-30, XLT-60, STH Default: NO TRANSDUCER Temperature Source Source of the temperature reading used to adjust the speed of sound.
  • Page 72 FAST (10 m/min) Default: SLOW (0.1 m/min) Use a setting just faster than the maximum filling or emptying rate (whichever is greater). Slower settings provide higher accuracy, faster settings allow for more rapid level fluctuations. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 73 The Flow Slope used in the flow calculation formula. Value Range: -999.000 to 9999.000 Default: 0.000 Roughness Coefficient (PMD = ROUND PIPE) The Flow Roughness Coefficient used in the flow calculation formula. Value Range: -999.000 to 9999.000 Default: 0.000 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 74 Thin Plate Rectangular Weir BS-3680 APPROACH WIDTH B CREST WIDTH B CREST HEIGHT P Rectangular Weir Contracted CREST WIDTH B Round Pipe PIPE INSIDE DIAMETER D Palmer Bowlus Flume MAXIMUM FLUME WIDTH HMAX H-Flume MAXIMUM LISTED HEAD HMAX SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 75 Options NO DIGITS, 1 DIGIT, 2 DIGITS, 3 DIGITS Default: NO DIGITS Low Flow Cutoff Eliminates totalizer activity for head levels at or below the cutoff value. Value Range: 0.000 to 60.000 Default: 0.000 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 76: Pump Control

    The introduction screen is displayed only on the device when using the local push buttons. This screen is not part of the Quick Start when using SIMATIC PDM. Shows the type of Wizard to be executed. Options CANCEL, START SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 77 See Pump Control Mode (Page 185) 2.7.1.4. for descriptions of each. Service Ratio Pump 1 Selects pump usage based on the RUN time ratio rather than last used. Value Range: 0 to 255 Default: 1 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 78 Units (2.1.1.) (Page 168) Value Range: 0.000 to 99999.000 Default: 0.000 ON Setpoint Pump 2 The level at which Pump 2 turns ON defined in Units (2.1.1.) (Page 168) Value Range: 0.000 to 99999.000 Default: 0.000 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 79: Accuracy

    1. Perform an auto sensor offset (Auto Sensor Offset (2.2.6.) (Page 173)) 2. Then perform an auto sound velocity (Auto Sound Velocity (2.12.1.6.) (Page 219)) Note The order is important - the auto sensor offset must be done before the auto sound velocity. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 80: Requesting An Echo Profile

    . Device Address Setting a device address is not necessary for local operation, but must be set if configuring the SITRANS LUT400 for use on a HART network. See Device Address (4.1.) (Page 260). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 81: Testing The Configuration

    Sensor measurement units. High Calibration Point Process full level. Low Calibration Point 15.0 Process empty level. Response Rate SLOW Sets Fill Rate / Empty Rate to 0.1 m/minute. see Fill Rate per Minute (2.3.1.) (Page 174) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 82: Flow Application Example

    The Parshall Flume is considered an exponential device, therefore the supplier’s data sheet includes a flow exponent value of 1.522. The SITRANS LUT400, and the XRS-5 transducer have been installed 1.6 m above the channel beside the TS-3 external temperature sensor.
  • Page 83 This prevents flow from being totalized when the head level reaches the ineffective point of the PMD. Refer to the PMD data sheets for ratings. Continue with alarm setup below. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 84 1 has been allocated to the Fail-safe alarm. Relay Logic (2.11.4.6.) Normally Open Default for control relay functions is Normally Open. (Page 217) In this example, relay 2’s coil will be Normally Open, and will close for 0.2 seconds. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 85: General Operation

    Commissioning (Page 50). Starting measurement The SITRANS LUT400 is a single point device. The device starts in LEVEL mode with a preset of no transducer and a low calibration point of 60 meters. Change the following common parameters to reflect your application.
  • Page 86: Dimensions

    7.1.1.3 Fail-safe The fail-safe parameters ensure that the devices controlled by the SITRANS LUT400 default to an appropriate state when a valid level reading is not available. (See list of faults that result in fail-safe in General Fault Codes (Page 269).) ●...
  • Page 87: General Introduction

    General Operation 7.2 Relays 7.2.1 General introduction Three relays are provided on the SITRANS LUT400. Each relay may be independently assigned to one function (one or more functions for alarms), and has a corresponding status icon on the LCD. ①...
  • Page 88: Relay Function

    Value ON and inactive when the flowrate falls below High Flowrate Value OFF. In low alarm, the alarm state becomes active when the flowrate falls below Low Flowrate Value ON and inactive when the flowrate rises above Low Flowrate Value OFF. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 89: Pump

    ● Low Level ● In-bounds Level ● Out-of-bounds Level ● High Flow Rate ● Low Flow Rate. Note A dedicated alarm exists for fail-safe condition as described above. See Fail-safe Fault Alarm (Page 102). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 90: Pump Relays

    The External Sampler relay operates the same as the External Totalizer relay described above. The periodic timeout-click will also continue to occur in fail-safe. Communications relays Relays controlled by communications (HART) are not affected by a fail-safe condition. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 91: Relay States

    General Operation 7.2 Relays 7.2.4 Relay states The relays on the SITRANS LUT400 are programmable, allowing for many control schemes. Relay types Relay 1 – NO / NC (Form C) Relay 2,3 – NO (Form A) 7.2.4.1 Relay output logic Affects relay reaction.
  • Page 92 High Flowrate Value ON (2.8.9.2.) (Page 204) (Page 204) High Flowrate Value OFF (2.8.9.3.) (Page 205) Low Flowrate Alarm Low Flowrate Value ON (2.8.10.2.) (Page 205) (2.8.10.) (Page 205) Low Flowrate Value OFF (2.8.10.3.) (Page 206) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 93: Relays Controlled By Hart Communications

    HART, contact your Siemens representative. Discrete Inputs SITRANS LUT400 has two discrete inputs to trigger or alter the way SITRANS LUT400 controls devices. A Backup Level Override, Pump Interlock, or a Switch (DI) Alarm can be configured using discrete inputs, and discrete input logic can be reversed if necessary for the application.
  • Page 94: Basic Operation

    LUT400 discrete input logic parameters (see Discrete Input Logic (2.9.2) (Page 208) ). 7.3.1.2 Backup Level Override parameters Example: SITRANS LUT400 is configured for a level measurement. In the same application, Discrete Input 2 is connected to a Hi Level Backup switch at a level value of 4.3 m. Parameter Sample Value Level Override Value (2.9.1.2) (Page 208)
  • Page 95: Effect Of Backup Level Override

    7.3.2 Pump Interlocks Discrete inputs can be used to supply pump information to the SITRANS LUT400 to set actions that will occur when a pump is determined to be in a failed state. For an example of how to configure a pump interlock, see Pump Control Interlocks (Page 112).
  • Page 96: Ma Control

    Control 7.4.1 mA output The SITRANS LUT400 has one mA output, used for communications with other devices. Example: Configuring the mA output to send a 4 to 20 mA signal corresponding to a scaled value of 10% to 90% of maximum process level on a 60 m transducer:...
  • Page 97: Verifying The Ma Range

    (2.2.1.) (Page 171) in its calculations of volume. Some vessel shapes also require extra dimensions to calculate the volume. Do not estimate these values. They must be correct to ensure the accuracy of your volume calculations. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 98 • The default reading changes to a range from 0 to 100 • The process empty value is still measured to the bottom of the vessel (Low Calibration Point (2.2.1.) (Page 171) plus any Far Range (2.2.5.) (Page 172)), not the top of Dimension A. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 99: Characterization Chart

    Note The end points in the curve are 0,0 (fixed) and the point defined by Maximum Level and Maximum Volume. 7.5.3.1 Example chart (with 15 of possible 32 Level and Volume breakpoints defined): SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 100 Linear approximation uses a linear algorithm; curved approxima- Volume 11 tion uses a cubic spline algorithm. Volume 12 Volume 13 10.9 Volume 14 13.0 Volume 15 15.0 See also Level 1 (2.6.7.1.) (Page 183) Volume 1 (2.6.7.2.) (Page 183) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 101: Alarms

    Units (2.1.1.) (Page 168) Flowrate Units (2.15.3.7.) (Page 233) Low Calibration Point (2.2.1.) (Page 171) High Calibration Point (2.2.2.) (Page 172) Note When configuring alarms, more than one alarm can be assigned to the same relay. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 102: Level

    ● Activates alarm assigned to relay 3 when level is within range 0.3 to 1.3 m ● Resets alarm above 1.3 m or below 0.3 m Use Alarm State (2.8.4.5.) (Page 200) to view the current state of the In-bounds Level Alarm. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 103: Example: Setting An Out-Of-Bounds Level Alarm

    4. Set Assigned Relay (2.8.7.4.) (Page 203) to Relay 3. The high temperature alarm will not de-activate until the temperature falls to 28 °C. Use Alarm State (2.8.7.5.) (Page 203) to view the current state of the High Temperature Alarm. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 104: Switch (Discrete Input) Alarm

    1. Enable the Fail-safe Fault Alarm (set Enable (2.8.8.1.) (Page 204) = Enabled) 2. Set Assigned Relay (2.8.8.2.) (Page 204) to Relay 3. Use Alarm State (2.8.8.3.) (Page 204) to view the current state of the Fail-safe Alarm. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 105: Flowrate

    3. Set Low Flowrate Value OFF (2.8.10.3.) (Page 206) = 4 4. Set Assigned Relay (2.8.10.4.) (Page 206) to Relay 3 Pump Control The SITRANS LUT400 has the pump control functionality to solve nearly any water/waste Pump Control Wizard water application. To set up pump control for simple applications, see...
  • Page 106: Pump Control Algorithms

    (assist) or one pump at a time (backup). These six modes can be grouped into three main methods of pump control used by the SITRANS LUT400: Fixed, Alternate, and Service Ratio. The LUT420 (Level) model operates with Alternate pump control only.
  • Page 107: Set The Common Parameters

    ON Setpoint Pump 2 1.1 m* Sets the level at which pump 2 turns on. (2.7.1.8.) (Page 186) Sample values denoted by asterisks in illustration on Setting a pump down (wet well) group (Page 104). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 108: Set The Off Setpoints

    Sets the level at which pump 1 turns off. The first cycle will use Pump 1 (2.7.1.7.) this setpoint. Subsequent cycles rotate the setpoint among the (Page 186) pumps. OFF Setpoint 0.3 m** Sets the level at which pump 2 turns off. Pump 2 (2.7.1.9.) (Page 186) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 109: Set Relays To Fixed Duty Assist (Fda)

    ON Setpoint Pump 1 1.3 m Sets the level at which pump 1 turns on. (2.7.1.6.) (Page 186) ON Setpoint Pump 2 1.2 m Sets the level at which pump 2 turns on. (2.7.1.8.) (Page 186) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 110: Set Relays To Service Ratio Duty Assist (Sra)

    OFF Setpoint Pump 0.4 m Sets the level at which pump 1 turns off. 1 (2.7.1.7.) (Page 186) OFF Setpoint Pump 0.3 m Sets the level at which pump 2 turns off. 2 (2.7.1.9.) (Page 186) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 111: Set Relays To Service Ratio Duty Backup (Srb)

    OFF Setpoint Pump 0.4 m Sets the level at which pump 1 turns off. 1 (2.7.1.7.) (Page 186) OFF Setpoint Pump 0.3 m Sets the level at which pump 2 turns off. 2 (2.7.1.9.) (Page 186) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 112: Setting A Pump Up (Reservoir) Group

    7.7 Pump Control Note • The SITRANS LUT400 will not sacrifice other pumping strategies to ensure that the service ratio is held true. • If the pump ratios are set to the same value, then the ratio equals 1:1 and all pumps are used equally (default).
  • Page 113: Set The Common Parameters

    OFF Setpoint Pump 2 1.2 m** Sets the level at which pump 2 turns off. (2.7.1.9.) (Page 186) Sample values denoted by asterisks in illustration on Setting a pump up (reservoir) group (Page 110). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 114: Pump Control Interlocks

    (2.9.2.3) (Page 209) Input 2. These values will ensure that any pump reporting a failure is removed from the pumping rotation. For more information on pump interlocks and discrete inputs, see Discrete Inputs (Page 91). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 115: Other Pump Controls

    1. Display vessel volume on the LCD (set parameter Sensor Mode (2.1.2.) (Page 168) to VOLUME). 2. Toggle to SV on LCD to display current level (set parameter Sensor Mode Secondary (2.1.4.) (Page 170) to LEVEL). 3. See Running Totalizer (2.7.3.1.) (Page 194) to view pumped volume. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 116: Setting A Pump To Run-On

    Setting the pump start delays In the event that power to the SITRANS LUT400 has been lost, the pump start delay ensures that all of the pumps do not start at once to avoid power surges. There are two parameters used here: Pump Start Delay and Power Resumption Delay.
  • Page 117: Saving Energy

    The following example illustrates high energy cost usage reduction and/or elimination by using the SITRANS LUT400 Energy Savings function on a wet well (pump down application) using pump 1. Pre-requisite: enable Energy Savings function (set Enable (2.7.2.2.1.) (Page 189) =...
  • Page 118 Sets the high cost ON setpoint at process (Page 192) level of 9 m Peak OFF Setpoint Pump 1 (2.7.2.2.14.) Sets the high cost OFF setpoint at process (Page 192) level of 6 m SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 119: Tracking Pump Usage

    Sets relay 1 to be controlled by elapsed time (Page 213) Relay Logic (2.11.1.5.) Normally Use (if necessary) to change the behaviour of the (Page 213) Closed relay assigned to the elapsed time control. Default: Normally Open SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 120: Flow

    External totalizers are simple counters which count the number of relay clicks produced by the SITRANS LUT400. This is generally used to keep track of OCM or pumped volume totals. Note that both of these values are also stored in the SITRANS LUT400 and are available through communications.
  • Page 121: Relay Contacts

    Vessel Shape (2.6.1.) (Page 180) = Totalizers (2.16.) Flowrate Units (2.15.3.7.) NONE (Page 237) (Page 233) Vessel Shape (2.6.1.) (Page 180) = any Totalizers (2.7.3.) Volume Units (2.6.2.) setting other than NONE (Page 194) (Page 181) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 122: Flow Sampler

    Click once every 4310 units Interval (2.11.4.3.) (Page 217) Sets the INTERVAL (in hours) of the relay con- tact, usually long. Relay Duration (2.11.4.4.) Sets the DURATION (in seconds) of the relay (Page 217) contact, usually short. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 123: Open Channel Monitoring (Ocm)

    (Maximum Head (2.15.3.3.) (Page 232) and Maximum Flow at 20 mA (2.15.3.4.) (Page 232) at 20 mA). Vessel Type Standard Weirs (Page 124) Parshall Flume (Page 126) Leopold Lagco Flume (Page 127) Cut Throat Flume (Page 128) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 124: Method Of Flow Calculation

    7.11.1 Method of Flow Calculation When using the SITRANS LUT400 in a flow application, the Method of Flow Calculation (2.15.3.1.) (Page 231) must be selected. There are two possible methods for calculating flow with the SITRANS LUT400: absolute or ratiometric, and different information must be entered for the device to carry out the calculation.
  • Page 125: Setting Zero Head

    Low Calibration Point (2.2.1.) (Page 171) level in normal operation without reporting an LOE. The value is added to Low Calibration Point (2.2.1.) (Page 171) and can be greater than the range of the transducer. The examples on the following pages show both methods. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 126: Pmds With Exponential Flow To Head Function

    7.11.4.1 Standard Weirs ① Transducer ② 3 to 4 * h ③ 7.11.4.2 Applicable weir profiles ① V-notch or triangular ② Suppressed rectangular ③ Cipolleti or trapezoidal ④ Sutro or proportional SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 127 Flowrate Units (2.15.3.7.) (Page 233) Far Range (2.2.5.) (Page 172) K Factor (2.15.4.1.) (Page 235) Values are samples only. Consult weir manufacturer’s documentation for correct flow exponent. Required for exponential device absolute calculation only. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 128: Parshall Flume

    Flow Exponent (2.15.3.2.) (Page 231) 1.522–1.607 Maximum Head (2.15.3.3.) (Page 232) Maximum Flow at 20 mA (2.15.3.4.) (Page 232) K Factor (2.15.4.1.) (Page 235) Typical Flow Exponent range for Parshall Flume; consult your flume documentation. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 129: Leopold Lagco Flume

    Zero Head Offset (2.15.3.5.) (Page 233) Flowrate Units (2.15.3.7.) (Page 233) K Factor (2.15.4.1.) (Page 235) Typical Flow Exponent for Leopold Lagco Flume; consult your flume documentation. Required for exponential device absolute calculation only. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 130: Cut Throat Flume

    Plan View Application Information ● Similar to Parshall flume except that the floor is flat bottomed and throat has no virtual length. ● Refer to manufacturer’s specifications for flow equation and point of head measurement. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 131: Khafagi Venturi

    ● Similar to Parshall flume except that the floor is flat bottomed and the sidewalls are curved. ● For rated flows under free flow conditions, the head is measured 1 x (channel width) upstream from the beginning of the converging section. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 132 1.55 (Consult your flume documentation.) Maximum Head (2.15.3.3.) (Page 232) Maximum Flow at 20 mA (2.15.3.4.) (Page 232) Flowrate Units (2.15.3.7.) (Page 233) K Factor (2.15.4.1.) (Page 235) Required for exponential device absolute calculation only. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 133 Throat length (L) ⑥ Flow ⑦ Zero head ⑧ Hump height (p) ⑨ Height (h) * The transducer must be above the maximum head by at least the blanking value (see Near Range (2.2.4.) (Page 172)). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 134 Throat width (b) Hump Height (p) Throat length (L) Zero Head Offset (2.15.3.5.) (Page 233) Flowrate Units (2.15.3.7.) (Page 233) Method of Flow Calculation (2.15.3.1.) (Page 231) Maximum Flow at 20 mA (2.15.3.4.) (Page 232) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 135 Crest Height p Crest Length L Maximum Head (2.15.3.3.) (Page 232) Far Range (2.2.5.) (Page 172) Flowrate Units (2.15.3.7.) (Page 233) Method of Flow Calculation (2.15.3.1.) (Page 231) Maximum Flow at 20 mA (2.15.3.4.) (Page 232) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 136 Hump Height p Throat length L Maximum Head (2.15.3.3.) (Page 232) Far Range (2.2.5.) (Page 172) Flowrate Units (2.15.3.7.) (Page 233) Method of Flow Calculation (2.15.3.1.) (Page 231) Maximum Flow at 20 mA (2.15.3.4.) (Page 232) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 137 Throat Length (L) ⑥ Flow ⑦ Hump Height (p) ⑧ Zero head ⑨ Height (h) * The transducer must be above the maximum head by at least the blanking value (see Near Range (2.2.4.) (Page 172)). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 138 Hump Height p Throat Length L Maximum Head (2.15.3.3.) (Page 232) Far Range (2.2.5.) (Page 172) Flowrate Units (2.15.3.7.) (Page 233) Method of Flow Calculation (2.15.3.1.) (Page 231) Maximum Flow at 20 mA (2.15.3.4.) (Page 232) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 139 Crest Length (L) ⑤ Flow ⑥ Zero Head ⑦ Height (h) ⑧ Crest Height (p) * The transducer must be above the maximum head by at least the blanking value (see Near Range (2.2.4.) (Page 172)). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 140 Crest Height p Crest Length L Maximum Head (2.15.3.3.) (Page 232) Far Range (2.2.5.) (Page 172) Flowrate Units (2.15.3.7.) (Page 233) Method of Flow Calculation (2.15.3.1.) (Page 231) Maximum Flow at 20 mA (2.15.3.4.) (Page 232) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 141 Zero Head ⑥ Height (h) ⑦ Crest Width (b) ⑧ Crest Height (p) * The transducer must be above the maximum head by at least the blanking value (see Near Range (2.2.4.) (Page 172)). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 142 Crest Width b Crest Height p Maximum Head (2.15.3.3.) (Page 232) Far Range (2.2.5.) (Page 172) Flowrate Units (2.15.3.7.) (Page 233) Method of Flow Calculation (2.15.3.1.) (Page 231) Maximum Flow at 20 mA (2.15.3.4.) (Page 232) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 143 Range (2.2.4.) (Page 172)). Parameter Value Primary Measuring Device (PMD) (2.15.1.) (Page 230) BS-3680 Thin Plate V-Notch Weir PMD Dimensions (2.15.4.) (Page 234) Notch angle (a) Maximum Head (2.15.3.3.) (Page 232) Far Range (2.2.5.) (Page 172) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 144 General Operation 7.11 Open Channel Monitoring (OCM) Parameter Value Flowrate Units (2.15.3.7.) (Page 233) Method of Flow Calculation (2.15.3.1.) (Page 231) Maximum Flow at 20 mA (2.15.3.4.) (Page 232) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 145 7.11 Open Channel Monitoring (OCM) Rectangular Weir Contracted ① Approach width (B) ② 4 to 5 x h ③ Transducer ④ Flow ⑤ Zero head ⑥ Crest width (b) ⑦ Height (h) ⑧ Crest Height (p) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 146 Slope (fall/run) s Roughness Coefficient n Maximum Head (2.15.3.3.) (Page 232) Far Range (2.2.5.) (Page 172) Flowrate Units (2.15.3.7.) (Page 233) Method of Flow Calculation (2.15.3.1.) (Page 231) Maximum Flow at 20 mA (2.15.3.4.) (Page 232) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 147 Note Palmer Bowlus Flume can only be set up using ratiometric calculations. Application information ● Sized by pipe diameter D. ● Flume relief is trapezoidal. ● Designed to install directly into pipelines and manholes. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 148 Maximum Head (2.15.3.3.) (Page 232) Maximum Flow at 20 mA (2.15.3.4.) (Page 232) Flowrate Units (2.15.3.7.) (Page 233) Method of Flow Calculation (2.15.3.1.) (Page 231) Ratiometric Note H-Flume can only be setup using ratiometric calculations. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 149: Universal Calculation Support

    Head versus Flow (2.15.5.) (Page 236)) must be entered to define the flow. SITRANS LUT400 supports Universal curved (cubic spline) flow calculation shown in the following chart. (The Method of Flow Calculation (2.15.3.1.) (Page 231) for universal support can be Ratiometric or Absolute. Refer to your PMD manufacturer’s documentation.)
  • Page 150: Typical Flow Characterization

    32 breakpoints available for definition. Use as many breakpoints as required by the complexity of your PMD. See Volume (Page 95) for more information and parameter Universal Head versus Flow (2.15.5.) (Page 236) for characterization. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 151: Example Flumes

    7.11 Open Channel Monitoring (OCM) ① Zero Head ② Flow Breakpoints ③ Maximum Flow ④ Maximum Head ⑤ Head Breakpoints ⑥ Zero Head 7.11.4.9 Example flumes These example flumes would both require a universal calculation. Trapezoidal SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 152: Example Weirs

    General Operation 7.11 Open Channel Monitoring (OCM) Dual Range (nested) Parshall 7.11.4.10 Example weirs These weirs could require universal calculation. ① Compound ② Poebing ③ Approximate exponential SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 153: Trends

    • When a fail-safe condition has occurred, it will appear as a gap in the Trend line. • Trend view will not timeout. This view will display on LUI until the exit icon is selected. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 154: Data Logging

    7.13 Data logging The SITRANS LUT400 provides an extensive logging feature which can be viewed on the local display or downloaded to a PC through USB using the Web Browser tool. Enable data logging for a Process Value, an Alarm, or for Flow (see Data Logging (2.10.) (Page 210)).
  • Page 155: Simulation

    Yes to permanently delete all logs. 7.14 Simulation The SITRANS LUT400 supports simulation from the LUI. Level and discrete inputs can be simulated, separately or concurrently. Level Simulation In level simulation, the LCD reacts to the simulated level changes, and activates relays based on the setpoints programmed.
  • Page 156: Pump Relay Behaviour During Simulation

    Run Time parameter (see Pump Records (3.2.7.) (Page 243)). • If a pump start delay has been programmed for the device (Delay Between Starts (2.7.2.4.1.) (Page 194)), it will be respected in Simulation mode. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 157: Fail-Safe And Simulation

    1. Select the function to be simulated: Level or Discrete Input (can be simulated concurrently). 2. Set simulation parameters if performing a Level simulation. 3. Decide if pumps will be active during simulation (see Pump relay behaviour during simulation (Page 154)). 4. Start simulation. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 158: Simulating A Fixed Level

    Set parameter(s) for DI to be simulated (Discrete Input 1 (3.4.2.1.) (Page 259) and/or Discrete Input 2 (3.4.2.2.) (Page 259)) to Disabled if you do not wish to simulate a discrete input, or to stop DI simulation that is currently running. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 159: Simulation Timeout

    Troubleshooting (Page 267). If you cannot observe all possible operating conditions by varying the material level, use Simulation process (Page 155) to verify programming. Retest the system each time you adjust any control parameters. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 160: Sitrans Lut400 Communication Systems

    7.15 SITRANS LUT400 Communication Systems 7.15 SITRANS LUT400 Communication Systems The SITRANS LUT400 is an integrated level controller capable of communicating process information to a Supervisory Control and Data Acquisition (SCADA) system, through a HART modem. Figure 7-1 Communication via HART modem to SITRANS LUT400 7.15.1...
  • Page 161: Hart Multi-Drop Mode

    In order to configure a HART device, the configuration software requires the HART Electronic Device Description for the instrument in question. You can download the HART EDD for SITRANS LUT400 from the product page of our website. Go to: www.siemens.com/sitransLUT400 (www.siemens.com/sitransLUT400) and click on Support >...
  • Page 162: Configuring Communication Ports

    It is recommended that only HCF registered modems be used. Device Address The unique identifier of the SITRANS LUT400 on a HART network. Values Range: 0 to 63 (Set within range of 0 to 15 if HART 5 master used.) Default: 0 Set the device address or poll ID on a HART network.
  • Page 163: Remote Operation

    (www.siemens.com/simatic-pdm).) SIMATIC PDM features four Quick Start Wizards (Level, Volume, Volume-Linearization, and Flow) to easily configure the SITRANS LUT400. A Pump Control Wizard is also available. Other features include Echo Profile Utilities, Manual TVT Shaper adjustment, Auto False Echo Suppression screening, Process Variables monitoring, and Maintenance scheduling.
  • Page 164: Startup And Configuration

    8.1.1 Startup and Configuration To startup the SITRANS LUT400 using SIMATIC PDM, check that you have the latest version of PDM installed (update your installation if necessary - see SIMATIC PDM version (Page 162) SIMATIC PDM version below), then install the EDD. Next, configure the device using the Quick Start Wizards in PDM.
  • Page 165: Operation Via Web Browser (Usb)

    8.2.2 Startup and Configuration To start up the SITRANS LUT400 using the Web Browser, you must first install the USB driver and web browser interface. On the small DVD shipped with the device you will find the driver and installation software .
  • Page 166: Operation Via Ams Device Manager (Hart)

    8.3.2 Startup and Configuration To startup the SITRANS LUT400 using AMS Device Manager, you must first install the EDD (see below). You can then configure the device using the Quick Start Wizards in AMS. For more information on AMS functions, and details on how to configure the device using AMS, refer to the LUT400 Communications manual Communications for SITRANS LUT400 (HART) Manual (7ML19985NE01).
  • Page 167: Operation Via Field Communicator

    Features and Functions The FC375/FC475 HART Communicator is a handheld communication device that is easy to use, and provides universal support for other HART devices, such as the SITRANS LUT400. HART FC375/FC475 For a list of parameters available with the Field Communicator, see...
  • Page 168: Startup And Configuration

    8.5.2 Startup and Configuration To startup the SITRANS LUT400 using an FDT, you must first install the DTM (see below). You can then configure the device using the parameters available with the FDT. The full process to configure a field device via FDT is outlined in an application guide for SITRANS DTM, which can be downloaded from the product page of our website.
  • Page 169: Parameter Reference (Lui)

    . Press to return to Measurement mode. Communications for SITRANS LUT400 (HART) Manual (7ML19985NE01) Parameters are identified by name and organized into function groups. See LCD menu structure (Page 308) for a chart. Parameters accessible via the local push buttons are preceded by a number. Parameters not preceded by a number are accessible only via remote operation.
  • Page 170: Wizards (1.)

    Wizards (1.) Several Wizards are available with the SITRANS LUT400. Wizards group together all the settings needed for a particular feature. All Wizards are available via the local push buttons, and many are also available via SIMATIC PDM under the Device menu.
  • Page 171: Sensor Mode (2.1.3.)

    Flowrate in an open channel in Flowrate Zero Head (zero flow level) Units Option available only on LUT430, LUT440. ① Distance ② Sensor reference point ③ High calibration point ④ Space ⑤ Level ⑥ Low calibration point ⑦ Far range SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 172: Sensor Mode Secondary (2.1.4.)

    LUT430 (Pump and Flow model), and LUT440 (OCM model). Sets the secondary measurement type to be used in the application. See Sensor Mode (2.1.3.) (Page 169) for illustration. 9.2.1.6 Transducer (2.1.6.) Specifies the Siemens transducer connected to the device. Options NO TRANSDUCER XRS-5 XPS-10...
  • Page 173: Frequency (2.1.7.)

    Distance from sensor reference point to Low Calibration Point defined in Units (2.1.1.) (Page 168). Values Range: 0.000 to 60.000 Default: 60.000 The point from which level measurement is referenced (see Sensor Mode (2.1.2.) (Page 168) for illustration). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 174: High Calibration Point (2.2.2.)

    This is sometimes referred to as blanking or a dead zone. Defined in Units (2.1.1.) (Page 168). Options Range: 0.000 to 60.000 Default: 0.300 9.2.2.5 Far Range (2.2.5.) Note Far Range can extend beyond the bottom of the vessel. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 175: Auto Sensor Offset (2.2.6.)

    2. Measure the actual distance (for example, with a tape measure). 3. Enter the actual distance, defined in Units (2.1.1.) (Page 168). The deviation between the calculated and the actual distance value is stored in Sensor Offset (2.2.3.) (Page 172). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 176: Rate (2.3.)

    9.2.3.1 Fill Rate per Minute (2.3.1.) Defines the maximum rate at which the reported level is allowed to increase. Allows you to adjust the SITRANS LUT400 response to increases in the actual material level. Options Range: 0.000 to 99999.000 m/min Default: 0.100 m/min...
  • Page 177: Fail-Safe (2.4.)

    9.2.4 Fail-Safe (2.4.) The fail-safe parameters ensure that the devices controlled by the SITRANS LUT400 default to an appropriate state when a valid level reading is not available. The PV region on LUI will display dashes (– – – – – – –) until the fail-safe fault has been cleared. (See General Fault Codes (Page 269) for a list of faults that will cause failsafe.)
  • Page 178: Current Output (2.5.)

    Head, defined in Flowrate Units (2.15.3.7.) (Page 233). When Current Output Function is set to Manual, a power cycle will reset this parameter to its previous value. Option available only on LUT430, LUT440. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 179 Zero head ⑥ Head ⑦ Material surface ⑧ Maximum head Refer to PMD supplier documentation for maximum head. To modify Current Output Function via SIMATIC PDM: Open the menu Device – Select Analog Output. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 180: Ma Setpoint (2.5.3.)

    Minimum mA Limit (2.5.5.) Prevents the mA output from dropping below this minimum level for a measurement value. This does not restrict the Fail-safe or Manual settings. Values Range: 3.5 to 22.8 mA Default: 4.0 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 181: Maximum Ma Limit (2.5.6.)

    Values Range: 3.5 to 22.8 mA 9.2.6 Volume (2.6.) Carries out a volume conversion from a level value. Note Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 182: Vessel Shape (2.6.1.)

    Flat end horizontal cylinder PARABOLIC BOTTOM maximum volume, dimension A HALF SPHERE BOTTOM maximum volume, dimension A FLAT SLOPED BOTTOM maximum volume, dimension A PARABOLIC ENDS/ maximum volume, dimension A, di- Parabolic end horizontal cylinder mension L SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 183: Volume Units (2.6.2.)

    Determines volume measurement units used when Sensor Mode (2.1.2.) (Page 168) set to VOLUME. Options L (Litres) USGAL (US Gallons) IMPGAL (Imperial Gallons) CUM (Cubic Meters) USER DEFINED (units defined in User Defined Unit (2.6.6.) (Page 182)) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 184: Maximum Volume (2.6.3.)

    Level values are defined in Units (2.1.1.) (Page 168). Volume values are defined in Volume Units (2.6.2.) (Page 181). Level Values Range: 0.000 to 60.000 Default: 0.000 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 185 5. Under Table 1-8, go to Volume 1 (2.6.7.2.) (Page 183) to enter the volume value for the breakpoint 1. 6. Repeat steps 3 to 5, until values have been entered for all required breakpoints. Communications for SITRANS LUT400 (HART) Manual (7ML19985NE01) Level 1 (2.6.7.1.) 1. Press RIGHT arrow to open Edit mode.
  • Page 186: Pumps (2.7.)

    Table 25-32 (2.6.10.) 9.2.7 Pumps (2.7.) Note Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated. For details on relay behaviour under fail-safe conditions, see Pump relays (Page 88). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 187: Basic Setup (2.7.1.)

    FIXED DUTY ASSIST (FDA) At fixed ON and OFF setpoints and allows multiple pumps to run FIXED DUTY BACKUP (FDB) At fixed ON and OFF setpoints and allows only one pump to run SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 188 The level at which Pump 2 turns OFF, defined in Units (2.1.1.) (Page 168). Values Range: 0.000 to 99999.000 Default: 0.000 This parameter is set according to level even when another reading, such as volume, is shown on the LCD. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 189: Modifiers (2.7.2.)

    Note • The SITRANS LUT400 will not sacrifice other pumping strategies to ensure that the ratio is held true. • If the pump relays are set to the same value then the ratio equals 1:1 and all pumps are used equally (default).
  • Page 190 Available only on LUT430 (Pump and Flow model), and LUT440 (OCM model). Use these parameters to maximize your device’s operation during periods of low energy cost and minimize its operation during periods of high cost. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 191 Options DISABLED ENABLED Peak Lead Time (2.7.2.2.2.) The time in minutes before the Peak Start Time that the SITRANS LUT400 will begin pumping. Values Range: 0 to 65535 Default: 60 This value determines when pumping should start to ensure the level is as far as possible from the ON Setpoint Pump 1 (2.7.1.6.) (Page 186).
  • Page 192 Range: 00:00 to 23:59 Format: HH:MM (24 hour format, for example: for 5:30pm, set parameter to 17:30) Default: 00:00 Used in conjunction with Peak 3 End Time (2.7.2.2.8.) (Page 191) to define the high cost period. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 193 Range: 00:00 to 23:59 Format: HH:MM (24 hour format, for example: for 5:30pm, set parameter to 17:30) Default: 00:00 Used in conjunction with Peak 5 End Time (2.7.2.2.12.) (Page 192) to define the high cost period. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 194 Sets the process point at which Pump 2 will turn off when in a peak period. Values Range: 0.000 to 99999.000 Default: 0.000 To stop the pump(s) before the normal relay OFF Setpoint and reduce pump-running time. Enter the value to be used for the high cost period. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 195 Also be sure that this value does not overlap with Run-On Interval (2.7.2.3.2.) (Page 193). Pump Start Delays Available only on LUT430 (Pump and Flow model), and LUT440 (OCM model). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 196: Totalizers (2.7.3.)

    Running Totalizer (2.7.3.1.) Current pumped volume totalizer value in Volume Units (2.6.2.) (Page 181). Values Range: 0.00 to 999999999 Default: 0.00 Pumped volume is automatically calculated whenever both Volume and Pumps are configured. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 197 NO ADJUSTMENT No inflow adjustment is made (assumes an inflow of zero). For an illustration, see Pump Totalizers (Page 301). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 198: Alarms (2.8.)

    Options 9.2.8 Alarms (2.8.) The SITRANS LUT400 supports eight alarm types. Any alarm can be assigned to any available relay. It is possible to assign more than one alarm to the same relay. In this case, the relay will activate if any one of the alarms is activated. If no alarms are activated, the relay will become inactive.
  • Page 199: Low Level Alarms (2.8.2.)

    Enables/disables Low Level Alarm. Options ENABLED DISABLED Low Level Value ON (2.8.2.2.) Sets the material level (defined in Units (2.1.1.) (Page 168)) at which the Low Level Alarm will activate. Values Range: 0.000 to 99999.000 Default: 0.000 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 200: Switch (Discrete Input) Alarm (2.8.3.)

    (Discrete Input State (2.8.3.3.) (Page 199)). Enable (2.8.3.1.) Enables/disables Switch Alarm. Options ENABLED DISABLED Discrete Input Number (2.8.3.2.) Determines which discrete input to monitor for Switch Alarm. Options DISCRETE INPUT 1 DISCRETE INPUT 2 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 201: In-Bounds Level Alarm (2.8.4.)

    In-bounds Level Alarm (2.8.4.) Reported when material level is within a user-defined range (see High Level Value (2.8.4.2.) (Page 200) and Low Level Value (2.8.4.3.) (Page 200)). Enable (2.8.4.1.) Enables/disables In-bounds Level Alarm. Options ENABLED DISABLED SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 202: Out-Of-Bounds Level Alarm (2.8.5.)

    Out-of-bounds Level Alarm (2.8.5.) Reported when material level is outside a user-defined range (see High Level Value (2.8.5.2.) (Page 201) or Low Level Value (2.8.5.3.) (Page 201)). Enable (2.8.5.1.) Enables/disables Out-of-bounds Level Alarm. Options ENABLED DISABLED SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 203: Low Temperature Alarm (2.8.6.)

    Reported when process temperature is within a user-defined range (see Low Temperature Value ON (2.8.6.2.) (Page 202) or Low Temperature Value OFF (2.8.6.3.) (Page 202)). Enable (2.8.6.1.) Enables/disables Low Temperature Alarm. Options ENABLED DISABLED SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 204: High Temperature Alarm (2.8.7.)

    Value ON (2.8.7.2.) (Page 203) or High Temperature Value OFF (2.8.7.3.) (Page 203)). The temperature used for the alarm is the same temperature used for sound velocity compensation (see Temperature Source (2.12.1.3.) (Page 218)). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 205: Fail-Safe Fault Alarm (2.8.8.)

    Alarm State (2.8.7.5.) Read only. Used to view the current state of the High Temperature Alarm. Options ACTIVE INACTIVE 9.2.8.8 Fail-safe Fault Alarm (2.8.8.) Reported when fault that has caused a fail-safe condition is present. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 206: High Flowrate Alarm (2.8.9.)

    Options ENABLED DISABLED High Flowrate Value ON (2.8.9.2.) Sets the flowrate value (defined in Flowrate Units (2.15.3.7.) (Page 233)) at which the High Flowrate Alarm will activate. Values Range: 0.000 to 99999.000 Default: 0.000 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 207: Low Flowrate Alarm (2.8.10.)

    Options ENABLED DISABLED Low Flowrate Value ON (2.8.10.2.) Sets the flowrate value (defined in Flowrate Units (2.15.3.7.) (Page 233)) at which the Low Flowrate Alarm will activate. Values Range: 0.000 to 99999.000 Default: 0.000 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 208: Relay Logic (2.8.11.)

    Use to change the behaviour of Relay 1 when assigned to an alarm. Options NORMALLY OPEN NORMALLY CLOSED Relay 2 Logic (2.8.11.2.) Use to change the behaviour of Relay 2 when assigned to an alarm. Options NORMALLY OPEN NORMALLY CLOSED SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 209: Time To Spill (2.8.12.)

    9.2.9 Discrete Inputs (2.9.) Discrete inputs are used to trigger or alter the way SITRANS LUT400 controls devices such as pumps and alarms. Discrete inputs can be used for the following: ● as a backup level override ●...
  • Page 210: Backup Level Override (2.9.1)

    Discrete Input Logic (2.9.2) Use the following parameters to configure the discrete input itself. Normal state is standard operation, with the SITRANS LUT400 sensing the material level and controlling the pumps, and no faults or alarms present. The discrete input contacts are either NORMALLY OPEN or NORMALLY CLOSED when the system state is normal.
  • Page 211: Pump Interlock (2.9.3.)

    Available only on LUT430 (Pump and Flow model), and LUT440 (OCM model). Discrete inputs allow you to supply pump information to the SITRANS LUT400 so that it can modify pump algorithms. The following parameters are used to program actions that should take place when a pump is determined to be in a failed state.
  • Page 212: Data Logging (2.10.)

    If Fill and Stop, when new entries are added, the logging system stops. Options FIRST IN FIRST OUT FILL AND STOP 9.2.10.2 Process Value Log (2.10.2.) Enable (2.10.2.1.) Enables/disables Process Value (PV) Logging. Options ENABLED DISABLED SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 213: Alarm Log (2.10.3.)

    Menu number 2.10.4.2. visible on LUT440 (OCM model). Sets flow log mode. Options FIXED RATE VARIABLE PERCENTAGE MAX FLOW / MIN VARIABLE PERCENTAGE MAX FLOW VARIABLE PERCENTAGE MAX HEAD Option available only for LUT440. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 214: Delete Logs (2.10.5.)

    Delete Logs (2.10.5.) Select YES to permanently delete all data logs in the LUT400. Options 9.2.11 Other Control (2.11.) Note Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 215: Elapsed Time Relay (2.11.1.)

    Determines the relay assigned to elapsed time control. Options RELAY 1 RELAY 2 RELAY 3 Relay Logic (2.11.1.5.) Use to change the behaviour of the relay assigned to elapsed time control. Options NORMALLY OPEN NORMALLY CLOSED SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 216: Time Of Day Relay (2.11.2)

    The time in seconds from one change of state in the relay to the next. Values Range: 1 to 99999 Default: 10 Assigned Relay (2.11.2.4.) Determines the relay assigned to time of day control. Options RELAY 1 RELAY 2 RELAY 3 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 217: External Totalizer (2.11.3)

    Use to scale the external totalizer up or down as required. Values Range: 0.0000001 to 99999 .000 Default: 1.000 This allows the totalizer relay to click for different values of volume. Example: To click once every 4310 units, set 2.11.3.2. Multiplier to 4310. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 218: External Sampler (2.11.4.)

    Miscellaneous relays (Page 88).) Note Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated. Enable (2.11.4.1.) Enables/disables flow sampler relay control. Options ENABLED DISABLED SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 219 By default a control contact is Normally Open. For Interval (2.11.4.3.) (Page 217) the corresponding relay coil is energized. By setting this parameter to Normally Closed, the relay coil will be de-energized for the duration phase. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 220: Signal Processing (2.12.)

    EXTERNAL TS-3 AVERAGE OF SENSORS (Transducer and TS-3) With this default, the SITRANS LUT400 uses the transducer’s internal temperature sensor (standard in all Siemens EchoMax Transducers). If the transducer does not have an internal temperature sensor, Fixed Temperature value, or an External TS-3 temperature sensor can be used.
  • Page 221 Condition for use of this feature: ● The acoustic beam atmosphere is other than air ● The acoustic beam atmosphere temperature is unknown ● The Reading accuracy is acceptable at higher material levels only. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 222: Echo Select (2.12.2.)

    (Page 245) exceeds Echo Threshold (2.12.2.2.), the echo is accepted as a valid echo and is evaluated. Values Range: -20 to 128 Default: 5 Use this feature when an incorrect material level is reported. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 223: Tvt Setup (2.12.3.)

    LOE Timer expires or the device will enter fail- safe condition (see Fail-Safe (2.4.) (Page 175)). 9.2.12.3 TVT Setup (2.12.3.) Note Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 224 (2.12.3.) (Page 221) > Auto False Echo Suppression (2.12.3.1.), and press RIGHT arrow to open Edit Mode. 5. Select Learn. The device will automatically revert to On (Use Learned TVT) after a few seconds. Communications for SITRANS LUT400 (HART) Manual (7ML19985NE01) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 225: Tvt Shaper (2.12.4.)

    5 groups. (We recommend using SIMATIC PDM to access this feature.) To use TVT shaper via SIMATIC PDM: 1. Open the menu Device – Echo Profile Utilities and click on TVT Shaper. (For more details see TVT Shaper in LUT400 Communications manual SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 226: Measured Values (2.12.5.)

    3. Open TVT Breakpoint 1 enter the TVT Offset value (between –50 and 50). 4. Go to the next TVT Breakpoint and repeat steps c) and d) till all desired breakpoint values have been entered. Communications for SITRANS LUT400 (HART) Manual (7ML19985NE01) Breakpoint 1-8 (2.12.4.1.) Values Range: –50 to 50 dB...
  • Page 227 Corresponds to Head [the distance from Zero Head Offset (2.15.3.5.) (Page 233) to the monitored surface in Units (2.1.1.) (Page 168)]. Flow Measurement (2.12.5.6.) Available only on LUT430 (Pump and Flow model) and LUT440 (OCM model). The calculated flowrate, defined in Flowrate Units (2.15.3.7.) (Page 233). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 228: Display (2.13.)

    Adjust the value to improve visibility in different temperatures and luminosity. Available only via LUI and web browser. 9.2.14 Date and Time (2.14.) Enter the current date and time using the local push buttons. Parameter Edit mode displays a string editor. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 229: Date (2.14.1.)

    (including currently highlighted character) to end of text string 9.2.14.1 Date (2.14.1.) Date is the current date in the format: YYYY-MM-DD. Values Range: 1900-01-01 to 2155-12-31 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 230: Time (2.14.2.)

    The order of the day within the month when daylight saving will begin. Options FIRST, SECOND, THIRD, FOURTH FIRST Starting Day (2.14.3.3.) The day of the week on which daylight saving will begin. Options SUNDAY, MONDAY, TUESDAY, WEDNESDAY, THURSDAY, FRIDAY, SATURDAY SUNDAY SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 231: Flow (2.15.)

    SEPTEMBER, OCTOBER, NOVEMBER, DECEMBER JANUARY 9.2.15 Flow (2.15.) Available only on LUT430 (Pump and Flow model) and LUT440 (OCM model). Note Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 232: Primary Measuring Device (Pmd) (2.15.1.)

    1. Measure the actual head (e.g. with a tape measure or solid rule) 2. Enter the actual head value The deviation between the entered head value and the calibrated value, is stored in Zero Head Offset (2.15.3.5.) (Page 233). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 233: Basic Setup (2.15.3.)

    Maximum Head (2.15.3.3.) (Page 232) and Zero Head Offset (2.15.3.5.) (Page 233) and with the curve based on the specified exponent. ① Flow exponent The exponential equation is: Q = KH Flow Exponent (2.15.3.2.) Where: SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 234 Device (PMD) and works in conjunction with Maximum Head (2.15.3.3.) (Page 232) to define the highest point in the exponential curve. Use it when the PMD requires a maximum head and flow reference point. Maximum Flow must be set for all Absolute and Ratiometic PMDs. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 235 The volume units used to display total flow. Options L/S (Litres per second) L/MIN (Litres per minute) CUFT/S (Cubic feet per second) CUFT/D (Cubic feet per day) GAL/MIN (US Gallons per minute) GAL/D (US Gallons per day) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 236: Pmd Dimensions (2.15.4.)

    Crest height p - OCM Dimension 2 (2.15.4.6.) Crest length L - OCM Dimension 3 (2.15.4.7.) Trapezoidal Flume BS-3680 Approach width B - OCM Dimension 1 (2.15.4.5.) Throat width b - OCM Dimension 2 (2.15.4.6.) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 237 Use this parameter if the PMD is set to Exponential devices. The Constant Factor is used to create an exponential curve with end points set by Maximum Head (2.15.3.3.) (Page 232) and Zero Head Offset (2.15.3.5.) (Page 233) , and with the curve based on the specified exponent. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 238: Universal Head Versus Flow (2.15.5.)

    9.2.15.5 Universal Head versus Flow (2.15.5.) In the following table, enter Head and Flow Breakpoints for universal PMDs. Head Breakpoints: The head breakpoints for which flowrate is known, defined in Units (2.1.1.) (Page 168). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 239: Totalizers (2.16.)

    2.15.5.1.2. Flow 25 9.2.16 Totalizers (2.16.) Available only on LUT430 (Pump and Flow model) and LUT440 (OCM model). Note Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 240: Daily Totalizer (2.16.1.)

    Enter the factor (powers of 10 only) by which actual flow is divided, prior to display on LCD. Use a value such that the eight-digit totalizer doesn’t roll over between readings. Example: For an LCD Total display in 1000s of flow units, enter 1000. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 241: Reset Daily Totalizer (2.16.5.)

    Text that can be used in any way. A recommended use is as a unique label for a field device in a plant. Limited to 32 alphanumeric characters. 9.3.1.3 Descriptor (3.1.3.) Text that can be used in any way. Limited to 32 ASCII characters (16 ASCII characters via HART). No specific recommended use. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 242: Message (3.1.4.)

    Serial Number (3.1.8.) Read only. Unique factory set serial number of the device. 9.3.1.9 Final Assembly Number (3.1.9.) Integer used to identify the device on site, e.g. enter ’2’ to denote second SITRANS LUT400 in application. 9.3.1.10 Hardware Revision (3.1.10.) Read only.
  • Page 243: Loader Revision (3.1.12.)

    Read only. Corresponds to the Electronics Device Description (EDD) installed with the device. 9.3.1.13 Manufacture Date (Date of Manufacturing in PDM) (3.1.13.) The date of manufacture of the SITRANS LUT400 (YYYY-MM-DD). 9.3.1.14 Order Option (3.1.14.) Read only. Displays the device type: Standard or NAMUR 43-compliant.
  • Page 244: Trend (3.2.2.)

    In SIMATIC PDM, open the menu Device – Wear. 9.3.2.5 Power-on Time (3.2.5.) Displays the number of days the device has been powered on since manufacture. In SIMATIC PDM, open the menu Device – Wear. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 245: View Logs (3.2.6.)

    Therefore, the LUI operation can be changed (via Sensor Mode (2.1.2.) (Page 168)) without affecting the process being controlled. 9.3.2.7 Pump Records (3.2.7.) Relay usage. Run Time Relay 2 (3.2.7.1.) Read or set the total running time of Relay 2 in hours. Values Range: 0 to 999999 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 246: Temperature Peak Values (3.2.8.)

    This value measures the quality of the reported echo value: higher values represent better quality. This measure combines the noise level, quality of tracking, and signal strength. (For more details see Echo Processing (Page 291)) Values (view only) Range: 0 to 100 % SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 247: Maintenance (3.3.)

    Displays the peak ambient noise (in dB above 1 μV rms) of a noise profile after each measurement. 9.3.3 Maintenance (3.3.) Note Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated. 9.3.3.1 Transducer Enable (3.3.1.) Enables/disables transducer from taking measurements. Options ENABLED DISABLED SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 248: Backup Control (3.3.2.)

    The maintenance warnings and reminders are available through HART communications. This information can be integrated into an Asset Management system. For optimal use, we SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 249 Options HOURS DAYS YEARS Communications for SITRANS LUT400 (HART) Manual (7ML19985NE01) Units are selectable only via SIMATIC PDM, PACTware FDT, and AMS. Lifetime Expected (3.3.3.1.) Note The device always operates in years. Changing the Time Units affects only the parameter view of the Remaining Device Lifetime parameters in SIMATIC PDM, PACTware FDT, and AMS.
  • Page 250 2. Set Reminder Activation (3.3.3.4.) (Page 248) to the desired option. Maintenance Status (3.3.3.7.) Indicates which level of maintenance reminder is active. In SIMATIC PDM, open the menu View – Device Status, click on the Maintenance tab, and check the Device Lifetime Status window. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 251: Remaining Sensor Life (3.3.4.)

    To access these parameters via SIMATIC PDM: ● Open the menu Device – Maintenance and select the Remaining Sensor Lifetime tab. (For more details see Maintenance in LUT400Communications manual SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 252 Options HOURS DAYS YEARS Communications for SITRANS LUT400 (HART) Manual (7ML19985NE01) Units are selectable only via SIMATIC PDM, PACTware FDT, and AMS. Lifetime Expected (3.3.4.1.) Note The device always operates in years. Changing the Time Units affects only the parameter view of the Remaining Device Lifetime parameters in SIMATIC PDM, PACTware FDT, and AMS.
  • Page 253 2. Set Reminder Activation (3.3.4.4.) (Page 251) to the desired option. Maintenance Status (3.3.4.7.) Indicates which level of maintenance reminder is active. In SIMATIC PDM, open the menu View – Device Status, click on the Maintenance tab, and check the Sensor Lifetime Status window. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 254: Service Schedule (3.3.5.)

    SIMATIC PCS7 Asset Management Software in conjunction with SIMATIC PDM. To access these parameters via SIMATIC PDM: ● Open the menu Device – Maintenance and select the Service Schedule tab. (For more details see Maintenance in LUT400Communications manual SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 255 Options HOURS DAYS YEARS Communications for SITRANS LUT400 (HART) Manual (7ML19985NE01) Units are selectable only via SIMATIC PDM, PACTware FDT, and AMS. Service Interval (3.3.5.1.) Note The device always operates in years. Changing the Time Units affects only the parameter view of the Service Interval parameters in SIMATIC PDM, PACTware FDT, and AMS.
  • Page 256 2. Set Reminder Activation (3.3.5.4.) (Page 254) to the desired option. Maintenance Status (3.3.5.7.) Indicates which level of maintenance reminder is active. In PDM, open the menu View – Device Status, click on the Maintenance tab and check the Service Schedule Status window. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 257: Schedule (3.3.6.)

    To access these parameters via SIMATIC PDM: ● Open the menu Device – Maintenance and select the Calibration Schedule tab. (For more details see Maintenance in LUT400Communications manual SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 258 Options HOURS DAYS YEARS Communications for SITRANS LUT400 (HART) Manual (7ML19985NE01) Units are selectable only via SIMATIC PDM, PACTware FDT, and AMS. Calibration Interval (3.3.6.1.) Note The device always operates in years. Changing the units affects only the parameter view of the Calibration Interval parameters in SIMATIC PDM, PACTware FDT, and AMS.
  • Page 259 2. Set Reminder Activation (3.3.6.4.) (Page 257) to the desired option. Maintenance Status (3.3.6.7.) Indicates which level of maintenance reminder is active. In SIMATIC PDM, open the menu View – Device Status, click on the Maintenance tab and check the Calibration Schedule Status window. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 260: Simulation (3.4.)

    Simulates level changes, and activates relays based on the setpoints programmed. Level Simulation Enable (3.4.1.1.) Enables/disables level simulation. Options DISABLED ENABLED Level Value (3.4.1.2.) Enables/disables level simulation. Values Range: Low Calibration Point to High Calibration Point Default: 0.000 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 261: Discrete Inputs (3.4.2.)

    9.3.4.3 Pump Activations (3.4.3.) Sets how physical relays (that are assigned to pumps) will behave in simulation mode. Options DISABLED Pump relays are not activated in simulation ENABLED Pump relays are activated in simulation SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 262: Communication (4.)

    (as required by HART communications). Manufacturer’s ID Read only. Numerical code that refers to the manufacturer of the device (e.g. 42, which refers to Siemens). Device Id Read only. Unique identification of the device by manufacturer and device type.
  • Page 263: Security (5.)

    5.1 Write Protection. ● User PIN cannot be changed via communications. Note The User PIN value cannot be recovered in the field. Record a new user PIN in a secure manner. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 264: Language (6.)

    Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated. Selects the language to be used on the LCD. Options ENGLISH DEUTSCH FRANCAIS ESPANOL ITALIANO PORTUGUÊS русский Characteristics Certificates & Approvals Device Certification The approvals certificates applicable to the device. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 265: Service And Maintenance

    SITRANS LUT400 requires no maintenance or cleaning under normal operating conditions. 10.1 Firmware updates To update the LUT400 firmware, please contact your Siemens representative to obtain the installer (self-executable .exe file). For a complete list of representatives, go to http://www.siemens.com/processautomation (http://www.siemens.com/processautomation).
  • Page 266: Replacing The Battery

    4. Lift out battery. 5. Insert new battery and press down on face of battery to secure in holder. 6. Press down on plastic battery cover to secure in place. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 267: Disposal

    Dangerous Goods with special transport documentation. 10.6 Return procedure Enclose the bill of lading, return document and decontamination certificate in a clear plastic pouch and attach it firmly to the outside of the packaging. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 268 – Number of returned devices/replacement parts – Reason for returning the item(s) ● Decontamination declaration (http://www.siemens.com/sc/declarationofdecontamination) With this declaration you warrant "that the device/replacement part has been carefully cleaned and is free of residues. The device/replacement part does not pose a hazard for humans and the environment."...
  • Page 269: Diagnosing And Troubleshooting

    2. Verify that the wiring connections are correct. 11.1.2 Specifically 1. The SITRANS LUT400 is set to communicate via a HART modem but no communication is returning to the master. – Check that the device address is set correctly for the HART network.
  • Page 270: Device Status Icons

    Communication is good; device is in simulation • mode or works with substitute values. Out of operation • Communication is good; device is out of action. • Data exchanged • No data exchange • SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 271: General Fault Codes

    (see Fail-Safe (2.4.) (Page 175)) and LUI to display dashes (– – – – – – –) until fault is cleared. These faults are indicated with an asterisk (*) in the table below. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 272 Correct range calibration. • ing/other adverse process condi- tions, invalid calibration range. If fault persists, contact your • local Siemens representative. Cable fault. Inspect attached cabling and any termination points to ensure no Broken cable. disconnection or damage; re- pair/replace if necessary. If no issue with cabling, contact your local Siemens representative.
  • Page 273 Calibration interval as defined in Perform calibration. Maintenance Demanded Limit has expired. Internal device error. Reset power. If fault persists, contact your local Siemens rep- resentative. Submergence detected. Correct the installation. The transducer appears sub- merged. Incorrect product model.
  • Page 274 Copy the Error reading file. Unexpected log file to a computer and delete error. it from the device. Configuration error. Adjust/correct relay assignments or setpoints. One or more settings invalid. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 275: Common Problems Chart

    Meaning Corrective Action Icon PDM Icon Parameter backup did not suc- Repair required. Contact your ceed. local Siemens representative. Communication or file system problems. User input required. Manually force recovery. (Set parameter Backup Control Serial numbers mismatch. (3.3.2.) (Page 246).) Simulation Enabled.
  • Page 276 Replace if required, or use fixed temperature. See Temperature Source (2.12.1.3.) (Page 218). Vapours If fluctuation is unacceptable, consider an alternative technology. Contact your Siemens representative. Reading is fixed, but Incorrect speed of re- Verify response speed setting is adequate for...
  • Page 277 Verify setpoints. Relay not activating Relay incorrectly assigned Verify with simulation. See Simulation (3.4.) correctly (Page 258). Incorrect relay function Verify with simulation. See Simulation (3.4.) selected (Page 258). Incorrect relay setpoints Verify setpoints. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 278: Noise Problems

    (e.g. 8 m application using an 8 m XRS-5). Using a larger transducer with greater transmitted energy should help to improve performance in a noise condition. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 279: Determine The Noise Source

    If the measured noise is above 5 dB go to Non-Transducer Noise Sources below. 1. Connect only the shield wire of the transducer to the SITRANS LUT400. If the measured noise is below 5 dB, continue with the next step. If the noise is above 5 dB, go to Common Wiring Problems below.
  • Page 280: Common Wiring Problems

    ● Connections between the wire supplied with the transducer, and any customer installed extension wire should only be grounded at the LUT400. On Siemens transducers the white wire is negative and the black wire is positive. If the extension wire is colored differently, make sure that it is wired consistently.
  • Page 281: Measurement Difficulties

    If the LOE Timer (2.4.2.) (Page 175) expires due to a measurement difficulty, the Fail-Safe mA Value (2.4.3.) (Page 175) displays. In rare cases, the SITRANS LUT400 may lock on to a false echo and report a fixed or wrong reading.
  • Page 282: Increase Fail-Safe Timer Value

    2. Transducer is properly aimed 3. Transducer is not in contact with any metal object. 4. Material mixer (if used) is operating while the SITRANS LUT400 is operating. If it is stopped, ensure that the mixer blade is not stopped under the transducer.
  • Page 283: Nozzle Mountings

    11.7.3.1 If the Echo is Close to the Transducer If there is a static, incorrect, high level reading from the SITRANS LUT400 there is probably something reflecting a strong echo back to the transducer. If the material level never reaches that point extend the Near Range (2.2.4.) (Page 172) to a distance to just past the...
  • Page 284: Liquid Splashing

    If multiple echoes appear on the Echo Profile, typical of a flat material profile (especially if the vessel top is domed), use the “TF ” (True First) algorithm. Should a stable measurement still not be attainable, contact Siemens representative. 11.9...
  • Page 285: Poor Ring Down

    To assist in troubleshooting echo profiles, pan and zoom options are available. See Requesting an Echo Profile (Page 78). 11.11 Trend Display A trend display is available with pan and zoom options. See Trends (Page 151). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 286: Technical Data

    TS-3 temperature sensor, and a Low Calibration Point of 3 m or less. Under severe EMI/EMC environments per IEC 61326-1 the DC powered device may have an additional error increase of up to 0.5 mm. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 287: Interface

    PC running a web browser • PC running a Field Device Tool (FDT) • Field Communicator 375/475 (FC375/FC475) • Compatible transducers EchoMax series and STH series Transducer frequency 10 to 52 kHz Communication HART 7.0 • • SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 288: Mechanical

    Back mount bracket 190 mm (7.5") x 190 mm (7.5") x 9 mm (0.35") • Polycarbonate • Weight Enclosure with display lid: 1.3 kg (2.87 lbs) • Enclosure with blank lid: 1.2 kg (2.65 lbs) • SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 289: Environmental

    The device nameplate lists the approvals that apply to your device. General , CE, FM, UL listed, C-TICK US/C Hazardous Non-incendive (Canada) • CSA Class I, Div. 2, Groups A, B, C, D; Class II, Div 2, Groups F, G; Class • SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 290: Dimension Drawings

    Dimension drawings 13.1 SITRANS LUT400 Dimensions ① Back mount bracket ② Enclosure ③ Cable entry (3 places) SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 291: Cutout Dimensions (For Remote Panel Mount)

    13.2 Cutout Dimensions (for Remote Panel Mount) Note Cut-out template (printed to scale) shipped with remote panel mount model. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 292: Technical Reference

    Technical reference Principles of Operation The SITRANS LUT400 is a high quality ultrasonic controller, configured to meet the needs of different applications, from medium range solids applications to liquids management with open channel measurement capability. The LUT400 features our next generation of Sonic Intelligence®...
  • Page 293: Echo Processing

    TVT curve just once, a loss of echo may occur The SITRANS LUT400, with its advanced tracking ability, can find and track the real echo amongst stationary clutter echoes. Therefore, even if the echo drops below the tvt curve, it can be identified with near certainty for approximately 30 seconds.
  • Page 294: Algorithm

    Use in mid to long range solids applica- est, and First highest confidence value tions where the material return echo is based on the three criterion wide and large, and where competing (widest, highest, and first). smaller echoes challenge BLF. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 295: Confidence

    • For detailed instructions on using this feature via the local push buttons, see Shaper Mode (2.12.3.4.) (Page 223). Communications for SITRANS LUT400 (HART) Manual (7ML19985NE01) False echoes can be caused by an obstruction in the transducer shot path (such as pipes, ladders, chains).
  • Page 296 False echo ③ Material echo ④ Sensor reference point ⑤ High calibration point = 1 m ⑥ Obstruction at 13 m ⑦ Material level at 31 m ⑧ Low calibration point = 45 m SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 297: Measurement Range

    A.2.2 Measurement Range Near Range Near Range (2.2.4.) (Page 172) programs SITRANS LUT400 to ignore the area in front of the transducer. The default blanking distance is 27.8 cm (0.91 ft) from the sensor reference point. Near Range allows you to increase the blanking value from its factory default. But Shaper Mode (2.12.3.4.) (Page 223) is generally recommended in preference to extending the...
  • Page 298: Measurement Response

    In 5 time constants, the output rises exponentially: from 63.2% of the change in the first time constant, to almost 100% of the change by the end of the 5th time constant. Damping example: time constant = 2 seconds input (level) change = 2 m SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 299: Analog Output

    By default, the reported value depends on the device type. A standard device reports the last valid reading, and a NAMUR NE43 compliant device reports the user-defined value for Material Level (2.4.1.) (Page 175) (3.58 mA by default). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 300: Loss Of Echo (Loe)

    ● Units (2.1.1.) (Page 168), ● Volume conversion parameters - Volume (2.6.) (Page 179), Sensor Offset (2.2.3.) (Page 172), ● Flow parameters - Flow (2.15.) (Page 229), ● and/or Totalizer parameters - Totalizers (2.16.) (Page 237). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 301: Sound Velocity

    The sound velocity of the transmission medium is affected by the type, temperature, and vapor pressure of the gas or vapor present. As preset, the SITRANS LUT400 assumes the vessel atmosphere is air at +20 °C (+68 °F). Unless altered, the sound velocity used for the distance calculation is 344.1 m / s (1129 ft / s).
  • Page 302 ● two breakpoints very near the maximum level For combination curves, enter at least two breakpoints immediately before and after any sharp angle (as well as one breakpoint exactly at the angle) on the curve. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 303: Pump Totalizers

    Set option Based on pump cycle to calculate the inflow based on the change of volume between the end of the last pump cycle and the start of the next one, and the time period between the last cycle and the current one. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 304: Flow Calculation

    A.7.1 Method of Flow Calculation The SITRANS LUT400 can be programmed to use either of two methods for calculating flow from the head measurement: absolute or ratiometric. The result is the same regardless of the method used. The main difference is the information that must be entered in order for the device to carry out the calculation.
  • Page 305: Data Logging

    Log type Headings Alarms Date (YYYY/MMM/DD) Time (HH:MM:SS) Alarm Name Value at Transition Transition Value Units Alarm State Date (YYYY/MMM/DD) Time (HH:MM:SS) Head Head Units Flow SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 306 Daily Total Running Total Totalizer Units Date (YYYY/MMM/DD) Time (HH:MM:SS) PV Type PV Value PV Units Temperature Temperature Units To clear entries when log memory becomes full, see Viewing the Data Log (Page 152). SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 307: Technical Support

    In addition to our documentation, Siemens provides a comprehensive support solution at: ● Services & Support (http://www.siemens.com/automation/service&support) Personal contact If you have additional questions about the device, please contact your Siemens personal contact at: ● Partner (http://www.automation.siemens.com/partner) To find the personal contact for your product, go to "All Products and Branches" and select "Products &...
  • Page 308: List Of Abbreviations

    Volt NEMA National Electrical Manufacturer’s Association Process Device Manager Programmable Logic Controller Primary Variable measured value Resistance Capacitance resistance x capacitance µs SCADA Supervisory Control and Data Acquisition Silicon-controlled rectifier switching device SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 309 Long form Description Units SPDT Single Pole Double Throw relay configuration SPST Single Pole Single Throw relay configuration Secondary Variable equivalent value Time Varying Threshold sensitivity threshold Universal Serial Bus VSDs Variable Speed Drives SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 310: Lcd Menu Structure

    LOW CALIB. PT. RESPONSE RATE DIMENS. A DIMENS. L VOLUME UNITS MAX. VOLUME APPLY? 1.1.3 QS FLOW (LUT430, 440 only) INTRODUCTION TRANSDUCER TEMPERATURE SOURCE FIXED TEMPERATURE PRIMARY MEASURING DEVICE METHOD OF FLOW CALCULATION UNITS SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 311 2.1.3 SENSOR MODE (LUT430, 440) 2.1.4 SENSOR MODE SECONDARY (LUT420) 2.1.5 SENSOR MODE SECONDARY (LUT430, 440) 2.1.6 TRANSDUCER 2.1.7 FREQUENCY 2.1.8 LONG SHOT DURATION 2.1.9 SHORT SHOT DURATION 2.2 CALIBRATION 2.2.1 LOW CALIB. PT. 2.2.2 HIGH CALIB. PT. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 312 2.7.1 BASIC SETUP 2.7.1.1 PUMP CONTROL ENABLE 2.7.1.2 RELAY PUMP 1 2.7.1.3 RELAY PUMP 2 2.7.1.4 PUMP CONTROL MODE (LUT420) 2.7.1.5 PUMP CONTROL MODE (LUT430, 440) 2.7.1.6 ON SETPOINT PUMP 1 2.7.1.7 OFF SETPOINT PUMP 1 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 313 2.7.2.4.1 DELAY BETWEEN STARTS 2.7.2.4.2 POWER RESUMPTION DELAY 2.7.3 TOTALIZERS (LUT430, 440 only) 2.7.3.1 RUNNING TOTALIZER 2.7.3.2 TOTALIZER DECIMAL POSITION 2.7.3.3 TOTALIZER MULTIPLIER 2.7.3.4 INFLOW/DISCHARGE ADJUST 2.7.3.5 RESET RUNNING TOTALIZER 2.8 ALARMS 2.8.1 HIGH LEVEL ALARM SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 314 2.8.6.2 LOW TEMPERATURE VALUE ON 2.8.6.3 LOW TEMPERATURE VALUE OFF 2.8.6.4 ASSIGNED RELAY 2.8.6.5 ALARM STATE 2.8.7 HIGH TEMPERATURE ALARM 2.8.7.1 ENABLE 2.8.7.2 HIGH TEMPERATURE VALUE ON 2.8.7.3 HIGH TEMPERATURE VALUE OFF 2.8.7.4 ASSIGNED RELAY 2.8.7.5 ALARM STATE SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 315 2.9.3 PUMP INTERLOCK (LUT430, 440 only) 2.9.3.1 ENABLE PUMP 1 2.9.3.2 PUMP 1 DISCRETE INPUT 2.9.3.3 ENABLE PUMP 2 2.9.3.4 PUMP 2 DISCRETE INPUT 2.10 DATA LOGGING 2.10.1 LOGGING MODE 2.10.2 PROCESS VALUE LOG SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 316 2.11.3.5 RELAY LOGIC 2.11.4 EXTERNAL SAMPLER (LUT430, 440 only) 2.11.4.1 ENABLE 2.11.4.2 MULTIPLIER 2.11.4.3 INTERVAL 2.11.4.4 RELAY DURATION 2.11.4.5 ASSIGNED RELAY 2.11.4.6 RELAY LOGIC 2.12 SIGNAL PROCESSING 2.12.1 TEMPERATURE AND VELOCITY 2.12.1.1 SOUND VELOCITY SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 317 2.13 DISPLAY 2.13.1 LOCAL DISPLAY BACKLIGHT 2.13.2 LCD CONTRAST 2.14 DATE AND TIME 2.14.1 DATE 2.14.2 TIME 2.14.3 DAYLIGHT SAVING 2.14.3.1 ENABLE 2.14.3.2 STARTING ORDINAL 2.14.3.3 STARTING DAY 2.14.3.4 STARTING MONTH 2.14.3.5 ENDING ORDINAL SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 318 2.16.1 DAILY TOTALIZER 2.16.2 RUNNING TOTALIZER 2.16.3 TOTALIZER DECIMAL POSITION 2.16.4 TOTALIZER MULTIPLIER 2.16.5 RESET DAILY TOTALIZER 2.16.6 RESET RUNNING TOTALIZER 3. MAINTENANCE AND DIAGNOSTICS 3.1 IDENTIFICATION 3.1.1 TAG 3.1.2 LONG TAG 3.1.3 DESCRIPTOR SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 319 3.2.8.2 LOWEST VALUE 3.2.9 ECHO QUALITY 3.2.9.1 FIGURE OF MERIT 3.2.9.2 CONFIDENCE 3.2.9.3 ECHO STRENGTH 3.2.9.4 NOISE AVERAGE 3.2.9.5 NOISE PEAK 3.3 MAINTENANCE 3.3.1 TRANSDUCER ENABLE 3.3.2 BACKUP CONTROL 3.3.3 REMAIN. DEV. LIFE 3.3.3.1 LIFETIME EXPECTED SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 320 3.3.6.2 TIME LAST CALIB 3.3.6.3 TIME NEXT CALIB 3.3.6.4 REMINDER ACTIV. 3.3.6.5 REMIND. 1 (REQ.) 3.3.6.6 REMIND. 2 (DEM.) 3.3.6.7 MAINT STAT 3.3.6.8 ACK STATUS 3.3.6.9 ACK 3.4 SIMULATION 3.4.1 LEVEL 3.4.1.1 LEVEL SIMULATION ENABLE SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 321 3.4.1.3 RAMP 3.4.1.4 RAMP RATE 3.4.2 DISCRETE INPUTS 3.4.2.1 DISCRETE INPUT 1 3.4.2.2 DISCRETE INPUT 2 3.4.3 PUMP ACTIVATIONS 4. COMMUNICATION 4.1 DEVICE ADDRESS 5. SECURITY 5.1 WRITE PROTECTION 5.2 USER PIN 6. LANGUAGE SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 322: Glossary

    (decibel) a unit used to measure the amplitude of signals. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 323 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 324 TVT (time varying threshold) a time-varying curve that determines the threshold level above which echoes are determined to be valid. SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 325: Index

    Hotline, (Refer to Support request) pump interlock, 112 wiring, 92 Disposal, 265 distance calculation, 298 identifications and abbrevations list, 306 Documentation, 305 in bounds, 100 Instructions and manuals, 305 interlock pump, 112 echo select algorithm, 220 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 326 148 relay, 119 H-flume, 146 modifiers, parameters, 89 Khafagi Venturi flume, 129 relays, 84 Leopold Lagco flume, 127 response rate, 83, 296 parshall flume, 126 Return procedure, 265 universal calculation, 147 run on, 114 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 327 58 transducers, 38 time control, 117 time to spill, 207 totalizer, 119 transducers enable/disable, 245 transmit pulse, 290 trapezoidal, 149 trends, 151 troubleshooting noise problems, 276 TS-3, 39 universal example, 97 volume, 95 SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 328 Index SITRANS LUT400 Operating Instructions, 07/2019, A5E33329501-AC...
  • Page 330 For more information Level measurement: www.siemens.com/level Weighing and batching systems: www.siemens.com/weighing Siemens AG Process Industries and Drives Process Automation 76181 Karlsruhe Germany © Siemens AG 2019 Subject to change without prior notice Printed in Canada A5E33329501-AC...

Table of Contents