Current Output Function (2.5.3.); Ma Output Allocation (2.5.4.) - Siemens HydroRanger 200 HMI Operating Instructions Manual

Sitrans ultrasonic controllers
Hide thumbs Also See for HydroRanger 200 HMI:
Table of Contents

Advertisement

8.6.5.3

Current output function (2.5.3.)

Alters the mA output/measurement relationship.
Index
Options
Related
Altered by
8.6.5.4

mA output allocation (2.5.4.)

Sets the input source from which the mA output is calculated.
Index
Options
Related
Enter the point number the mA output is based on. This value depends on whether Current
Output Function (2.5.3.) (Page 181) is set as transducer or mA input.
For a single-point device, if Current Output Function (2.5.3) (Page 181) uses a transducer,
parameter mA Output Allocation (2.5.4) can only be altered if Sensor Mode (2.1.3.)
(Page 163) is set for DPD or DPA.
Parameter mA Output Allocation (2.5.4.) can be set to a particular point or range of points.
When set to a range of points, the mA output will be the average of the readings from all in
service transducers in the range. Out-of-service transducers will be ignored.
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
mA output
mA function
OFF
Level
Space
*Distance
Volume
Flow
Head
Volume Rate
mA Input
mA output allocation (2.5.4.) (Page 181)
Milliamp output (2.5.9.) (Page 182)
Sensor mode (2.1.3.) (Page 163)
mA Output
*Point 1
Point 2
Average of readings from Point 1 and Point 2
Point 3
Current output function (2.5.3.) (Page 181)
Parameter reference
Sensor mode (2.1.3.)
Level, differential, or average
Space
Distance
Level or space
OCM
8.6 Setup (2.)
181