A.11

Response rate

The device's ability to respond to material level changes is designed to exceed even the
most demanding installation requirements.
The Response rate (2.3.4.) (Page 174) setting automatically presets various parameters
affecting the device response to material level changes as follows:
LOE timer (2.4.2.) (Page 177) (min)
Fill rate/minute (2.3.2.) (Page 173) (m/min)
Empty rate/minute (2.3.3.) (Page 173)
(m/min)
Filling indicator (2.3.9.) (Page 176) (m/min)
Emptying indicator (2.3.10.) (Page 176)
(m/min)
Rate filter (2.3.5.) (Page 175) (option)
Fuzz filter (2.11.5.6.) (Page 236) (% of span) 100
Echo lock window (2.11.5.5.) (Page 235)
Scan delay (2.1.14.) (Page 167) (seconds)
Number of long shots (2.1.12.) (Page 167)
If any of these parameters are independently altered, a Response rate (2.3.4.) (Page 174)
parameter alteration automatically resets the independently altered value.
Slower Response rate (2.3.4.) (Page 174) provides greater measurement reliability.
Faster performance may be obtained by independently setting Fill rate/minute (2.3.2.)
(Page 173) and Empty rate/minute (2.3.3.) (Page 173). Maximum rates may be impeded by
Echo lock (2.11.5.4.) (Page 235),Scan delay (2.1.14.) (Page 167) and Shot delay (2.1.16.)
(Page 168) values.
A.12

Analog output

The mA output (current output) is proportional to material level in the range 4 to 20 mA. 0%
and 100% are percentages of the full-scale reading (m, cm, mm, ft, in). Typically, mA output
is set so that 4 mA equals 0% and 20 mA equals 100%.
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
Parameter (Units)
Values dependent on response rate
Slow
100
10
0.1
1
0.1
1
0.01
0.1
0.01
0.1
10 min. or 300
*1 min or 50 mm
mm (11.8 inch)
(2 inch)
50
(per Empty rate/minute (2.3.3.) (Page 173) /Filling
indicator (2.3.9.) (Page 176) and time since last valid
measurement)
5
5
10
5
Technical reference

A.11 Response rate

Medium
Fast
1
10
10
1
1
*1 min or 50
mm (2 inch)
10
3
2