Output Hold/Clear Setting Function - Mitsubishi Electric NZ2GF2S-60IOLD8 User Manual

Cc-link ie field network remote io-link module
Table of Contents

Advertisement

Output HOLD/CLEAR setting function

Whether to hold or clear the last SIO output and output process data can be set when the IO-Link module is disconnected
from data link or when the CPU module operating status is STOP.
• HOLD: Outputs the last output process data or SIO output
• CLEAR: Outputs 0 in SIO (source output) mode In IO-Link mode, a notification is issued to the IO-Link device about the
output process data being invalid. (Device operation following reception of a notification differs depending on the IO-Link
device.)
Operation mode
This function is enabled only in the following operation modes.
• IO-Link (standard) mode
• IO-Link (sink input) mode
• SIO (source output) mode
Output HOLD/CLEAR setting and its operation
When CLEAR or HOLD is set for an output, the output is turned on or off as follows.
ON/OFF status is indicated by CH Output data valid flag (RY8 to RYF) in IO-Link mode and by CH CQ output signal (RY0
to RY7) in SIO (source output) mode.
Operating status
Data link in
CPU module in RUN
operation
CPU module in STOP
CPU module in PAUSE
CPU module in RESET
CPU module suspended by
error
During disconnection/cyclic stop
• Remote input signal (RX) and remote output signal (RY) will be turned off regardless of this setting if a
moderate or major error occurs on the IO-Link module.
• Remote input signal (RX) and remote output signal (RY) will also be turned off regardless of this setting if a
channel error occurs.
7 FUNCTIONS
94
7.4 CC-Link IE Field Network Communication Function
Output HOLD/CLEAR setting
CLEAR
Last output status
Last output status
OFF
ON
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
HOLD
Last output status
Last output status
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON