Input response time setting function

This function prevents an incorrect input due to noise by setting the response time until the module recognizes an actual input
as the X signal.
Although tolerance to chattering and noise will increase with longer input response times, response to input
signals will be slowed.
Operation modes and data
This function is enabled only in the following operation modes and with the following data.
• IO-Link (sink input) mode: DI signals
• SIO (sink input) mode: CQ input signals
Setting method
Operating procedure
1.
Open the "CC IE Field Configuration" window.
[Navigation window]  [Parameter]  [Module Information]  [RJ71GF11-T2]  [Basic Settings]  [Network
Configuration Settings]
2.
Open the "Parameter Processing of Slave Station" window.
From the list of stations, select an IO-Link module  [CC IE Field Configuration]  [Online]  [Parameter Processing of
Slave Station].
3.
Set "Method selection" to "Write Parameters".
4.
Set "Input Response Time Setting".
Window
Displayed items
Item
Input Response Time Setting
Setting range
• 0: 0ms
• 2: 1.0ms
• 3: 1.5ms
• 4: 5ms
• 5: 10ms (Default value)
• 6: 20ms
• 7: 70ms
7
7 FUNCTIONS
85
7.2 Input Function