Mitsubishi Electric NZ2GF2S-60IOLD8 User Manual page 150

Cc-link ie field network remote io-link module
Table of Contents

Advertisement

Input data invalid flag
■Device number, remote input signal name
Device No.
RX8
RX9
RXA
RXB
RXC
RXD
RXE
RXF
■Description
The input data invalid flag turns on in any of the following cases.
• When an error is detected in the corresponding channel
• When data input to the corresponding channel is defined as invalid by the IO-Link device
• When the device replacement flag (address: 36CCH) for the corresponding channel is on
• When CH IO-Link device connection status flag (RX20 to RX27) for the corresponding channel is off
• When a moderate or major error occurs
• When Remote READY (RWr0.b11) is off
• When a minor hardware error (error code: 1811H) occurs
Occurrence of minor error
■Device number, remote input signal name
Device No.
RX19
■Description
Use to check whether a minor error has occurred even once.
Occurrence of minor error (RX19) can be cleared by turning on Occurrence of minor error clear request flag (RY19).
External power supply ready
■Device number, remote input signal name
Device No.
RX1A
■Description
Status of the external power supply is indicated.
This flag turns on when the external power supply is detected as being on.
This flag turns off when the external power supply is detected as being off.
Event status flag
■Device number, remote input signal name
Device No.
RX1D
■Description
This flag turns on when a new event occurs.
This flag turns off when reading of all events is completed by Event read request flag (address: 2D09H).
APPX
148
Appendix 1 Remote I/O Signals
Name
CH1 Input data invalid flag
CH2 Input data invalid flag
CH3 Input data invalid flag
CH4 Input data invalid flag
CH5 Input data invalid flag
CH6 Input data invalid flag
CH7 Input data invalid flag
CH8 Input data invalid flag
Name
Occurrence of minor error
Name
External power supply ready
Name
Event status flag