Setting method
Operating procedure
1.
Open the "CC IE Field Configuration" window.
[Navigation window] [Parameter] [Module Information] [RJ71GF11-T2] [Basic Settings] [Network
Configuration Settings]
2.
Open the "Parameter Processing of Slave Station" window.
From the list of stations, select an IO-Link module [CC IE Field Configuration] [Online] [Parameter Processing of
Slave Station].
3.
Set "Method selection" to "Write Parameters".
4.
Set "Device Validation Setting" for each channel.
Window
Displayed items
Name
Device Validation Setting
Setting range
• 0: Do not validate (Default value)
• 1: Compatibility Validation (vendor information and model name)
• 2: Identity Validation (vendor information, model name, and serial number)