Output Hold/Clear Setting Function - Mitsubishi Electric NZ2GN2B1-32D User Manual

Programmable controller cc-link ie tsn remote i/o module
Hide thumbs Also See for NZ2GN2B1-32D:
Table of Contents

Advertisement

8.2

Output HOLD/CLEAR Setting Function

Sets whether to hold or clear the last output value for the case when the I/O module is disconnected from data link, or when
the CPU module operating status is STOP.
Output HOLD/CLEAR setting and its operation
When HOLD or CLEAR is set for an output, the output is turned on or off as follows.
Operating status
Data link in operation
CPU module in RUN
CPU module in STOP
CPU module in PAUSE
CPU module in RESET
CPU module suspended by
error
During disconnection/cyclic stop
If a moderate or major error has occurred in the I/O module, output turns off regardless of the output HOLD/CLEAR setting.
Setting procedure
Set HOLD or CLEAR using the function setting switch 5 of I/O module.
Function setting switch 5
OFF
ON
The setting of the output HOLD/CLEAR setting function is determined by the status of function setting switch 5 when the I/O
module is powered on.
When the setting of function setting switch 5 is changed while the I/O module is on, a function setting switch 5 changed error
(error code: 0205H) occurs, and the changed setting of the output HOLD/CLEAR setting function is not applied.
The setting status of the output HOLD/CLEAR setting can be checked by Output HOLD/CLEAR setting status (RWr2.b3). For
details, refer to the following.
Page 117 Output HOLD/CLEAR setting status (RWr2.b3)
Output HOLD/CLEAR setting
CLEAR
Last output status
Last output status
OFF
ON
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
Output HOLD/CLEAR setting
CLEAR (Factory default)
HOLD
Output HOLD/CLEAR setting
HOLD
Last output status
Last output status
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
8 FUNCTIONS
8.2 Output HOLD/CLEAR Setting Function