Mitsubishi Electric NZ2GF2S-60IOLD8 User Manual page 186

Cc-link ie field network remote io-link module
Table of Contents

Advertisement

Number of output ON times integration value clear command
■Remote buffer memory address
Address
2E80H
■Description
Values stored in CH Number of output ON times integration value (address: 299EH to 29ADH) are cleared.
b15
b14
b13
0 (fixed)
CH ON: Commanded, OFF: Not commanded
■Operation of Number of output ON times integration value clear
When the bit of the corresponding channel of Number of output ON times integration value clear command (address: 2E80H)
is set to Commanded (ON), CH Number of output ON times integration value (address: 299EH to 29ADH) of the
corresponding channel is cleared.
CH1 Output ON times integration value
(address: 299EH, 299FH)
Output ON times integration value clear
command (address: 2E80H.b0)
Output ON times integration value clear
completion (address: 2E81H.b0)
(1) Number of output ON times integration value clear processing
(2) Periodically read and check the event history using the REMFR instruction.
■Clearing by turning on Number of output ON times integration value clear command
The number of output ON times integration value is cleared only once when the bit of the corresponding channel of Number of
output ON times integration value clear command (address: 2E80H) is set to Commanded (ON). The number of output ON
times integration function is executed while the specified bit remains set to Commanded (ON).
Output ON times integration value clear
command (address: 2E80H.b0)
CH1 CQ output signal (Y0)
CH1 Output ON times integration value
(address: 299EH, 299FH)
(1) The number of output ON times integration function operates even if Number of output ON times integration value clear command is left on.
APPX
184
Appendix 3 Remote Buffer Memory
b12
b11
b10
b9
Number of ON times integration value
OFF
OFF
Controlled by the IO-Link module
OFF
ON
OFF
121
Name
Number of output ON times integration value clear command
b8
b7
b6
CH8
CH7
Controlled by the IO-Link module
Controlled by the program
ON
ON
ON
ON
OFF
OFF
122
123
0
b5
b4
b3
CH6
CH5
CH4
0
OFF
ON
OFF
ON
OFF
OFF
1
2
(1)
b2
b1
b0
CH3
CH2
CH1