Event History List

This section lists the events saved by the IO-Link module.
System
Event code (hexadecimal)
00400H
00510H
00600H
00601H
00602H
00603H
00604H
00605H
00606H
00607H
0060FH
00610H
00E01H
00E02H
00C10H
00E00H
*1 The detection values shown are approximate values and may fluctuate depending on the operating environment. Fluctuation ranges are
as follows.
Channel supply voltage warning (18V or less): 16V to 18V
Temperature rise warning (135 or higher): 120 to 150
Operation
Event code (hexadecimal)
20100H
20200H
24001H
24300H
24301H
24305H
24306H
24309H
11 TROUBLESHOOTING
142
11.8 Event History List
Overview
Power-on/reset clear
Data link restart (cyclic transmission start)
Successful downloading of IO-Link device
parameters
IO-Link device connection
Uploading/downloading not performed
Successful uploading of IO-Link device parameters
Data storage buffer overflow
IO-Link device parameter download failure
IO-Link device parameter upload failure
IO-Link device access failure
IO-Link device event reception (clear)
IO-Link device event reception (occur)
Channel supply voltage warning (18V or less)
Temperature rise warning (135 or higher)
Data link stop (cyclic transmission stop)
IO-Link device firmware version mismatch
Overview
Error clear
Event history clear
Remote operation request reception
Device replacement start
Device replacement end
IO-Link module parameter setting
IO-Link device parameter setting
Manual upload request
Cause
The module was powered on or reset.
Own station data link resumed.
IO-Link device parameters were downloaded
successfully.
Connection with an IO-Link device was established
successfully.
Since the connected IO-Link device does not
support uploading and downloading functions, IO-
Link device parameters were not uploaded or
downloaded.
IO-Link device parameters were uploaded
successfully.
An IO-Link device with a parameter size that
exceeds IO-Link standards was connected.
Downloading of IO-Link device parameters failed.
Uploading of IO-Link device parameters failed.
Access to IO-Link device parameters failed.
A notification about event clear has been issued
from the IO-Link device.
A notification about event occurrence has been
issued from the IO-Link device.
*1
The channel supply voltage has decreased to a
warning level.
*1
The temperature of the channel has exceeded a
warning level.
Own station data link was stopped.
Parameters have been downloaded for an IO-Link
device with a firmware version different from that of
the module.
Cause
Errors were cleared.
Event history was cleared.
A remote operation request (RESET) was
received.
Device replacement was started.
Device replacement ended.
IO-Link module parameters were written.
IO-Link device parameters were written.
A manual upload request was issued.