11.4

Examples of Troubles with IO-Link Modules

Troubleshooting for input circuit

This section describes the troubleshooting for input circuit.
A signal incorrectly inputs data
■Cause
Noise is taken as input data.
■Action
• To prevent excessive noise, avoid installing power cables together with I/O cables.
• Connect surge absorbers to noise-generating devices such as relay and conductors using the same power supply or take
other noise reduction measures.

Troubleshooting for output circuit

This section describes the troubleshooting for output circuit.
A load momentarily turns on from off when the system is powered off
■Cause
When an inductive load is connected, the load [2] may turn on from off due to a sneak current of back EMF at the time of
shutoff [1].
IO-Link module
- Back electromotive force + [3]
Source output
CQ1
ON
CQ2
OFF
CQ8
+24V
24G
■Action
To suppress the back EMF, connect a diode parallel to the load where the back EMF is generated in [3].
- Back electromotive force +
Load
D1
D1 is as follows.
*1
Reverse voltage VR (VRM)
*2
Forward current IF (IFM)
*1 Approximately 10 times as large as the rated voltage in the specifications
Example: 24VDC  Approximately 200V
*2 Twice as much as the maximum load current (common) in the specifications or more
Example: 2A/1 common  4A or more
Load
[2]
Load
[1] Shut off
11 TROUBLESHOOTING
11.4 Examples of Troubles with IO-Link Modules
11
127