Ex.
When the input OFF delay function is disabled
External input device
connected to an
CQ1 terminal
CQ1
RX0
• The delay time does not include the hardware response time.
• The accuracy of the delay time is 0 to 400s.
Setting procedure
Operating procedure
1.
Open the "CC IE Field Configuration" window.
[Navigation window] [Parameter] [Module Information] [RJ71GF11-T2] [Basic Settings] [Network
Configuration Settings]
2.
Open the "Parameter Processing of Slave Station" window.
From the list of stations, select an IO-Link module [CC IE Field Configuration] [Online] [Parameter Processing of
Slave Station].
3.
Set "Method selection" to "Write Parameters".
4.
Set "Input OFF Delay Setting".
Window
Displayed items
Item
Input OFF Delay Setting
7 FUNCTIONS
84
7.2 Input Function
ON
OFF
OFF
ON
OFF
OFF
Send
Link scan time
Link scan time
OFF
Sends OFF.
[IO-Link module]
Send
Link scan time
Link scan time
[Master station]
Cannot recognize ON.
Setting range
• 0 (No delay)
• 1 to 150000 (400s to 60s, 400s unit)
Send
Link scan time
Link scan time