Cables
Use shielded cables for the cables which are connected to the module and run out from the control panel. If a shielded cable
is not used or not grounded correctly, the noise immunity will not meet the specified value.
■Cables for the CC-Link IE Field Network
Shielded cables should be used for the CC-Link IE Field Network. Strip a part of the jacket as shown below and ground the
exposed shield in the largest possible area.
(1) Cables for the CC-Link IE Field Network
(2) Shield
■Grounding the cable clamp
Use shielded cables for external wiring and ground the shields of the external wiring cables to the control panel with the
AD75CK cable clamp (manufactured by Mitsubishi Electric Corporation). (Ground the shield section 20 to 30cm away from
the module.)
(1)
AD75CK
(1) Module
(2) Inside a control panel
For detail on the AD75CK, refer to the following.
 AD75CK Cable Clamp Instruction Manual
External power supply
• Use a CE-marked product for an external power supply and always ground the FG terminal. (External power supply used
for the tests conducted by Mitsubishi Electric Corporation: IDEC PS6R-F24)
• Use a power cable of 10m or shorter when connecting it to the module power supply terminal.
• Use a power cable with a total length of 30m or less for connections to the external power supply.
• Use a power cable of 3m or less for connections from the external power supply terminal to the noise filter.
APPX
196
Appendix 6 EMC and Low Voltage Directives
(1)
(2)
(2)
(2)
20 to 30 cm