Mitsubishi Electric NZ2GF2S-60IOLD8 User Manual page 174

Cc-link ie field network remote io-link module
Table of Contents

Advertisement

Bit segment setting
■Remote buffer memory address
Address
1709H to 1719H
1809H to 1819H
1909H to 1919H
1A09H to 1A19H
1B09H to 1B19H
1C09H to 1C19H
1D09H to 1D19H
1E09H to 1E19H
■Description
The data (the number of segments, bit offset, bit length) used for the bit segment function is set. ( Page 78 Bit segment
function)
Ex.
The following shows settings for CH1 Bit segment setting (address: 1709H to 1719H).
n: 1 to 16
Address
b15
1709H
0 (fixed)
170AH
0 (fixed)
1719H
0 (fixed)
This setting is enabled only when the operation mode is the IO-Link mode.
■Number of segments
The number of segments is the number of times input process data is to be segmented. If the bit segmentation is not used, set
0.
■Bit length, bit offset
Set the bit length and bit offset of the input process data to be segmented in Bit length and Bit offset. Bit segmenting of input
process data is performed from the set offset position and at the bit number set for the bit length.
The No.2 bit length, No.2 bit offset (address: 170BH), and onwards will be enabled according to the value set
for the number of segments.
■Setting range
• Number of segments: The setting range is 0 to 16. (Default value: 0)
• Bit length: The setting range is 0 to 16. (Default value: 0)
• Bit offset: The setting range is 0 to 255. (Default value: 0)
■Enabling the setting
Turn on and off Operating condition setting request flag (address: 2D07H) to enable the setting.
APPX
172
Appendix 3 Remote Buffer Memory
b14
b13
b12
b11
No.1 bit length
No.16 bit length
Name
CH1 Bit segment setting
CH2 Bit segment setting
CH3 Bit segment setting
CH4 Bit segment setting
CH5 Bit segment setting
CH6 Bit segment setting
CH7 Bit segment setting
CH8 Bit segment setting
b10
b9
b8
b7
No.1 bit offset
No.16 bit offset
b6
b5
b4
b3
Number of segments
b2
b1
b0