Precautions
■Precautions before parameter settings
For the precautions before parameter settings, refer to the following.
GX Works3 Operating Manual
GX Works2 Version 1 Operating Manual (Common)
■Precautions for parameter settings
• When using the IO-Link module, always enable the station-based block data assurance. When it is disabled, correct
operation of the IO-Link module cannot be guaranteed. For details on the block data assurance per station, refer to the
following: User's manual for the master/local module used.
• Do not set the parameter using the CCPASET instruction in the master station. Correct operation of the IO-Link module
cannot be guaranteed because the module operates with the station-based block data assurance disabled when the
CCPASET instruction is executed. (The CCPASET instruction is intended to configure parameters for a master/local
module. For details on the CCPASET instruction, refer to the user's manual for the master/local module used.)
6 PARAMETER SETTING
44
6.1 CC-Link IE Field Network Parameter Setting