When the IO-Link module is replaced while the module is
powered on
The following shows the procedure for replacing an IO-Link device with another IO-Link device in a state that the IO-Link
module power supply is on.
The replacement procedure may differ depending on conditions. ( Page 190 Condition)
Replacement procedure
 Set "Device Validation Setting" to "0: Do not validate".
Page 70 IO-Link device validation function
 Set the target channel using the "Start Device Changeout" of "Command Execution of Slave Station".
Page 99 Device Replacement Function
 Remove the connected IO-Link device, and replace it with a new IO-Link device.
Page 39 Wiring of IO-Link terminal block and external devices
 Create or change a program. Skip this step if not creating programs or making changes.
Page 105 PROGRAMMING
 Set the target channel using the "Device Changeout Complete" of "Command Execution of Slave Station".
Page 99 Device Replacement Function
 Return "Device Validation Setting" back to the original setting.
 Configure the parameter setting of the IO-Link device.
Page 54 IO-Link Device Parameter Setting
 Check the event history for errors and confirm that events are being stored as intended.
Page 132 Method for Checking the Event History
 Restart the control.
Condition
Device validation
setting
Not validate
Compatibility validation
APPX
190
Appendix 4 IO-Link Device Replacement Procedure
New IO-Link
IO-Link device parameter used after
device
replacement
Compatible
When IO-Link device parameters are downloaded from the
non-volatile memory of the IO-Link module
When IO-Link device parameters are uploaded from the
new IO-Link device
When IO-Link device parameters are newly set
Incompatible
When IO-Link device parameters are downloaded from the
non-volatile memory of the IO-Link module
When IO-Link device parameters are uploaded from the
new IO-Link device
When IO-Link device parameters are newly set
Compatible
When IO-Link device parameters are downloaded from the
non-volatile memory of the IO-Link module
When IO-Link device parameters are uploaded from the
new IO-Link device
When IO-Link device parameters are newly set
Incompatible
When IO-Link device parameters are downloaded from the
non-volatile memory of the IO-Link module
When IO-Link device parameters are uploaded from the
new IO-Link device
When IO-Link device parameters are newly set
Replacement procedure
Set "Device Validation Setting" to "1.
Compatibility Validation (vendor information and
model name)".



Cannot be used.





Cannot be used.

Perform all procedures.