Function Setting Switch Setting - Mitsubishi Electric NZ2GF2S-60IOLD8 User Manual

Cc-link ie field network remote io-link module
Table of Contents

Advertisement

Function setting switch setting

Enable or disable the fast link-up function using the function setting switches on the front of the IO-Link module. The setting
made by the function setting switches becomes valid when the module is powered on. Thus, set these switches while the
module power is off.
For details on the fast link-up function, refer to the following.
Page 91 Fast link-up function
No.
Switch name
1
Function setting switch 1
(F LINK P1)
2
Function setting switch 2
(F LINK P2)
3
4
• To set the function setting switches, use a flathead screwdriver with a tip width of 0.9mm or less.
• Do not change the function setting switch while the module is powered on. Changing the function setting
switch while the module is powered on causes a minor error and flashes the ERR. LED. Returning the
function setting switch to the previous setting eliminates the error and turns off the ERR. LED.
5 INSTALLATION AND WIRING
30
5.2 Setting Switch
Function name
PORT1 fast link-up function
PORT2 fast link-up function
Use prohibited
Setting details
Enables or disables the fast link-up function of PORT1.
• On: Enable
• Off: Disable
Enables or disables the fast link-up function of PORT2.
• On: Enable
• Off: Disable
Always set to Off.