7.2
Input Function
Input OFF delay function
This function turns off an X signal after a predetermined time passed from when an actual input becomes off from on.
With the input OFF delay function, even an input whose ON time is shorter than that of the link scan can be surely recognized
on a program. When an external input device is replaced with a sensitive one, users can use the existing program only by
adjusting the delay time.
Operation modes and data
This function is enabled only in the following operation modes and with the following data.
• IO-Link (standard) mode: Data masking results
• IO-Link (sink input) mode: DI signals
• SIO (sink input) mode: CQ input signals
Description
Ex.
A short period of ON time can be surely recognized by setting the delay time longer than the period of the link scan time.
External input device
connected to an
OFF
CQ1 terminal
OFF
CQ1
Send
OFF
RX0
ON
OFF
ON
Send
Link scan time
Link scan time
ON
[IO-Link module]
Sends ON.
OFF delay
OFF delay
OFF
Send
Link scan time
Link scan time
[Master station]
Can recognize ON.
OFF
Link scan time
Link scan time
7 FUNCTIONS
83
7.2 Input Function
7