Mitsubishi Electric NZ2GF2S-60IOLD8 User Manual page 185

Cc-link ie field network remote io-link module
Table of Contents

Advertisement

Operating condition setting completion flag
■Remote buffer memory address
Address
2D08H
■Description
After the operation condition is changed, Operating condition setting completion flag (address: 2D08H) turns on.
Turn off Operating condition setting request flag (address: 2D07H) after Operating condition setting completion flag (address:
2D08H) is turned on.
For the timing of Not performed (OFF)  Request (ON)  Not performed (OFF) of Operation condition setting request flag
(address: 2D07H), refer to the following.
Page 181 Operating condition setting request flag
b15
b14
b13
b12
0 (fixed)
(1) ON: Completed, OFF: Not completed
Event read request flag
■Remote buffer memory address
Address
2D09H
■Description
When this flag is turned off and on, the oldest event among events that have not been checked will be read to Event data
(address: 2C00H to 2C04H).
b15
b14
b13
b12
0 (fixed)
(1) ON: Commanded, OFF: Not commanded
■Operation of Event read request flag
Each time this flag is turned off and on, one new event will be read to Event data (address: 2C00H to 2C04H).
Event status flag (RX1D) turns off when all events are read.
If this flag is turned from Not Commanded (OFF) to Commanded (ON) again after all events are read, Event
data (address: 2C00H to 2C04H) will be cleared.
Event read completion flag
■Remote buffer memory address
Address
2D0AH
■Description
This flag shows the completion status of Event read request flag (address: 2D09H).
Stored value
0H
1H
■Operation of Event read completion flag
When reading of the event has completed, Event read completion flag (address: 2D0AH) will be Completed (1).
When Event read request flag (address: 2D09H) is turned on and off, Event read completion flag (address: 2DA0H) turns off.
b11
b10
b9
b8
b11
b10
b9
b8
Name
Operating condition setting completion flag
b7
b6
b5
b4
Name
Event read request flag
b7
b6
b5
b4
Name
Event read completion flag
Event read completion flag
Not completed
Completed
Appendix 3 Remote Buffer Memory
b3
b2
b1
b0
(1)
b3
b2
b1
b0
(1)
APPX
183
A

Hide quick links:

Advertisement

Table of Contents
loading