Mitsubishi Electric NZ2GF2S-60IOLD8 User Manual page 138

Cc-link ie field network remote io-link module
Table of Contents

Advertisement

Error code
Classificati
(hexadecimal)
on
180EH
Minor error
*1
1810H
Minor error
1811H
Minor error
*2
3004H
Moderate
error
3005H
Moderate
error
3006H
Moderate
error
3008H
Moderate
error
11 TROUBLESHOOTING
136
11.7 Error Codes and Warning Codes
Error name
Description and
cause
Temperature rise error
The temperature of the
*3
(160 or higher)
channel has exceeded
an error level.
IO-Link device error
An error notification
notification reception
from the IO-Link device
has been received.
Minor hardware failure
A minor hardware
failure has occurred.
Non-volatile memory
An error was detected in
data error (module
the module operation
working information)
information stored in the
non-volatile memory.
Non-volatile memory
An error was detected in
error (parameter)
the parameter data
stored on the non-
volatile memory.
External power supply
The external power
OFF error
supply is off.
Parameter data error
Parameter data values
(out-of-range settings)
are out of range.
Action
Errors detectable in each
operation mode
(1)
Check the wiring of the power
supply and relevant channels,
as well as the power supply
equipment status, and
implement measures to
reduce noise. Check whether
the operating ambient
temperature is within
specification. If the same
error is shown again, a
module hardware failure may
exist. Please consult your
local Mitsubishi
representative and explain
the symptom in details.
Check the error code shown
in the error code details with
the manual for the IO-Link
device.
Implement measures to
reduce noise. If the same
error is shown again, a
module hardware failure may
exist. Please consult your
local Mitsubishi
representative and explain
the symptom in details.
If the same error occurs
again, it is a module hardware
failure. Please consult your
local Mitsubishi
representative and explain
the symptom in details.
Reset the parameters being
used. If the same error occurs
again, it is a module hardware
failure. Please consult your
local Mitsubishi
representative and explain
the symptom in details.
Check the status of the
external power supply. If the
error occurred during system
start-up, please start the
external power supply first. If
the error occurred during
system shut-down, please
turn off the external power
supply last.
Check the parameters shown
in the error code details and
configure the settings again if
necessary.
(2)
(3)
(4)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents