Analog Output Hold/Clear Function - Mitsubishi Electric NZ2GFCE-60DAV8 User Manual

Cc-link ie field network digital-analog converter module (e-con type)
Table of Contents

Advertisement

7.6
This function allows the selection of whether to hold or clear the analog value output when the CPU module is in the following
operating status: RUN, STOP, or a stop error.
Combination of analog output status
The following table shows how the analog output status changes, depending on the combination of settings for D/A
conversion enable/disable setting (address: 0102H) and CH Output enable/disable flag (RY10 to RY17).
D/A conversion enable/disable setting (address:
0102H)
CH Output enable/disable flag (RY10 to RY17)
Analog output HOLD/CLEAR setting (address:
0105H to 0106H)
Analog output status while the CPU module is in RUN
Analog output status while the CPU module is in STOP
Analog output status while the CPU module is in stop error
Analog output status while the D LINK LED is off
Analog output status while the instruction of data link stop is
received from the master station
Analog output status while reserved from the master station
Analog output status of when the out-of-range digital value
error occurs
Analog output status of when the out-of-range setting error
occurs
Analog output status of when a hardware failure
*1 The analog output HOLD/CLEAR function may be executed even when the D LINK LED is on if the cyclic data update watch time is set.
For details, refer to the following:
Page 57 Cyclic Data Update Watch Function
*2 Indicates the case that the operation of a program is not completed within the expected time in the CPU module due to a hardware
failure in the D/A converter module or other factors. In this case, Remote READY (RXB) turns off and the RUN LED of the D/A converter
module goes out.
Downloaded from
ManualsNet.com

Analog Output HOLD/CLEAR Function

*1
*2
occurs
search engine
Enable
Enable
HOLD
CLEAR
The analog value D/A-converted from the
digital value is output.
Hold
Offset value
Hold
Offset value
Hold
Offset value
Hold
Offset value
Hold
Offset value
The upper limit value or lower limit value of
analog value is output.
0V/0mA
0V/0mA
0V/0mA
0V/0mA
Disable
Disable
Enable or disable
HOLD or CLEAR
HOLD or CLEAR
Offset value
0V/0mA
Offset value
0V/0mA
Offset value
0V/0mA
Offset value
0V/0mA
Offset value
0V/0mA
Offset value
0V/0mA
Offset value
0V/0mA
0V/0mA
0V/0mA
0V/0mA
0V/0mA
7 FUNCTIONS
7.6 Analog Output HOLD/CLEAR Function