Ethernet cable
For the specifications of the Ethernet cable, refer to the following.
 User's manual for the master/local module used
IO-Link cable
For details on IO-Link cables, refer to the following.
Page 35 Wiring with terminal block for module power supply and FG
Available software
The following software is available for settings and diagnostics of the IO-Link module. ( Manuals of each software)
Product name
GX Works2
GX Works3
MELSOFT Navigator
FDC
M_CommDTM-IOLink
IODD DTM Configurator
When the latest software is required, please consult your local Mitsubishi representative.
Applicable profile
To use the parameter setting function of an IO-Link module, the profile is required.
The profile is a setting file that stores information required for the start-up, operation, and maintenance of devices supporting
the CC-Link family.
A module is added to "Module List" of the "CC IE Field Configuration" window by profile registration to an engineering tool. For
the profile registration, refer to the operating manual for the engineering tool used.
Applicable devices
Up to eight IO-Link devices and SIO devices can be connected in combination to the IO-Link module.
The IO-Link mode and SIO mode can be set separately on the channels of the IO-Link module.
Refer to the following for operation modes supported by connected external devices.
Operation mode
Disabled mode
IO-Link (standard) mode
IO-Link (sink input) mode
SIO (sink input) mode
SIO (source output) mode
Power supply mode
For error codes and warning codes detectable in each operation mode, refer to the following.
Page 134 List of error codes and the warning codes
Functions/applications
Software for system design, programming, debugging, and maintenance of the programmable controller.
Integrated application of GX Works2 and GX Works3.
Application for DTM.
Description
Select this mode when no devices are connected.
An error is not detected when a channel in disabled mode is operating.
Select this mode to communicate with IO-Link devices. Process data is sent
and received at the following communication speeds.
• COM1: 4.8kbps
• COM2: 38.4kbps
• COM3: 230.4kbps
Select this mode to connect a source-type IO-Link device. In addition to IO-
Link (standard) mode, digital input is also supported.
Select this mode to connect a source-type SIO (input) device. This mode
communicates with general devices and supports digital input.
Select this mode to connect a sink-type SIO (output) device. This mode
communicates with general devices and supports digital input.
Select this mode to supply power to the device of another channel.
An error in the power line is only detected when a channel in power supply
mode is operating.
For setting examples and wiring methods, refer to the following.
Page 42 Using IO-Link devices that require power supplies for their
multiple terminals
4 SYSTEM CONFIGURATION
25
4.1 Applicable Systems
4