Output ON/OFF information hold function

This function checks if the output has been turned once on or off.
Operation mode
This function is enabled only in the following operation modes and with the following data.
• SIO (source output) mode
Output ON information
Output ON information is stored in CH Output ON information (RWr4.b0, RWr14.b0, RWr24.b0, RWr34.b0, RWr44.b0,
RWr54.b0, RWr64.b0, RWr74.b0).
Whether the output has been turned on or not can be checked with CH Output ON information (RWr4.b0, RWr14.b0,
RWr24.b0, RWr34.b0, RWr44.b0, RWr54.b0, RWr64.b0, RWr74.b0).
CH Output ON information (RWr4.b0, RWr14.b0, RWr24.b0, RWr34.b0, RWr44.b0, RWr54.b0, RWr64.b0, RWr74.b0) can
be cleared with CH Output ON information clear request (RWw4.b0, RWw14.b0, RWw24.b0, RWw34.b0, RWw44.b0,
RWw54.b0, RWw64.b0, RWw74.b0).
Output OFF information
Output OFF information is stored in CH Output OFF information (RWr4.b1, RWr14.b1, RWr24.b1, RWr34.b1, RWr44.b1,
RWr54.b1, RWr64.b1, RWr74.b1).
Whether the output has been turned off or not can be checked with CH Output OFF information (RWr4.b1, RWr14.b1,
RWr24.b1, RWr34.b1, RWr44.b1, RWr54.b1, RWr64.b1, RWr74.b1).
CH Output OFF information (RWr4.b1, RWr14.b1, RWr24.b1, RWr34.b1, RWr44.b1, RWr54.b1, RWr64.b1, RWr74.b1) can
be cleared with CH Output OFF information clear request (RWw4.b1, RWw14.b1, RWw24.b1, RWw34.b1, RWw44.b1,