■Description
Up to 16 errors (15 minor/moderate errors, 1 major error) of the module are recorded.
Ex.
The following shows the content stored in Current error data 1 (address: 2B00H to 2B0FH).
Address
b15
b14
2B00H
Error code
2B01H
2B02H
System area
2B03H
First two digits of the year
2B04H
Month
2B05H
Hour
2B06H
Second
2B07H
Error code details 1
2B08H
Error code details 2
2B09H
Error code details 3
2B0AH
System area
2B0FH
Item
Error code
First two digits of the year/Last two digits of the
year
Month/Date
Hour/Minute
Second
Error code details 1
Error code details 2
Error code details 3
*1 Those values show example when the error occurs at 10:35:40, August 29th, 2012.
*2 The clock information of the error that occurred is based on the clock information acquired from the CPU module of the master station.
When an error has occurred before the clock information is acquired from the CPU module, the error time is not recorded.
It is stored in the same format as Current error data 2 to Current error data 16 (address: 2B10H to 2BFFH) and Current error
data 1 (address: 2B00H to 2B0FH).
For the error code, refer to the following.
Page 134 Error Codes and Warning Codes
■Storage order of error data
The latest error is stored in Current error data 1 (address: 2B00H to 2B0FH).
Errors that occurred up to this time are stored in Current error data 2 to Current error data 16 (address: 2B10H to 2BFFH) in
reverse chronological order.
When 15 minor and moderate errors are stored in Current error data, new minor and moderate errors that
occur are stored in the IO-Link module.
When 15 minor and moderate errors are stored, even if one error is eliminated, the minor and moderate errors
saved inside the IO-Link module are stored.
If the same cause of errors occur continuously, only the error that occurred first is stored.
Also, new errors that occur after a major error are not held.
b13
b12
b11
b10
b9
Description
The error code for the error that occurred is stored.
The items on the left are stored in BCD code.
The detailed information of some errors is stored.
The data to be stored depend on the error. (
Page 134 Error Codes and Warning Codes)
b8
b7
b6
b5
b4
Last two digits of the year
Date
Minute
00H (Fixed)
Storage example
2012H
0829H
1035H
4000H
Appendix 3 Remote Buffer Memory
b3
b2
b1
b0
*1
APPX
179
A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents