6.3

Changing the IO-Link Module Parameters

This section describes the procedure for changing the parameter.
The precautions for changing the parameter are the same as those in the following section.
Page 43 CC-Link IE Field Network Parameter Setting
Changing the network configuration
When changing the network configuration diverting the created project, set the parameter in the following procedure.
Operating procedure
1.
Power off the module.
2.
Connect the modules again according to the desired network configuration.
3.
Power on the module.
4.
Open the "CC IE Field Configuration" window.
[Navigation window]  [Parameter]  [Module Information]  [RJ71GF11-T2]  [Basic Settings]  [Network
Configuration Settings]
5.
Drag and drop a module to set the IO-Link module. Input a numerical value to set the station number of the station.
Change the value as necessary.
6.
Open the "Parameter Processing of Slave Station" window.
From the list of stations, select an IO-Link module  [CC IE Field Configuration]  [Online]  [Parameter Processing of
Slave Station].
6 PARAMETER SETTING
48
6.3 Changing the IO-Link Module Parameters