Appendix 5.4.7
(1) Differences between High Performance model QCPU and Universal model
QCPU
(a) High Performance model QCPU
External input/output can be forcibly turned on/off on the screen opened by selecting [Online]  [Debug] 
[Forced Input Output Registration/Cancellation] in programming tool.
(b) Universal model
The external input/output forced on/off function is not supported in the Universal model
QCPU.
External input/output can be forcibly turned on/off by using the replacement program described below.
(2) Method of replacing High Performance model QCPU with Universal model
QCPU
As shown in below, add programs, "SETX" and "SETY", in the Program tab of the PLC parameter dialog box.
The following table shows the program setting of the "SETX" and "SETY".
Program name
SETX
SETY
Note Appx.5
Universal
Before executing this function with the Q02UCPU, Q03UDCPU, Q04UDHCPU, Q06UDHCPU, Q13UDHCPU, or
Q26UDHCPU, check the versions of the CPU module and GX Developer used.
(
Page 465, Appendix 2)
558
External input/output forced on/off function
QCPUNote Appx.5
Note Appx.5
Execution type
Scan
Scan
Position where program is added
Start of Program setting (No.1)
End of Program setting