MULTI-STEP SPEED CONTROL APPLICATION
4.4.3
INPUT SIGNALS (CONTROL KEYPAD: MENU M2 -> G2.2)
Table 26: Input signals, G2.2
Index
Parameter
P2.2.1 ***
Start/Stop logic
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
Min
Max
Unit
0
6
Default
Cust
ID
0
300
VACON · 77
Description
Logic = 0
Ctrl sgn 1 = Start
forward
Ctrl sgn 2 = Start
reverse
Logic = 1
Ctrl sgn 1 = Start/
Stop
Ctrl sgn 2 = Reverse
Logic = 2
Ctrl sgn 1 = Start/
Stop
Ctrl sgn 2 = Run
enable
Logic = 3
Ctrl sgn 1 = Start
pulse (edge)
Ctrl sgn 2 = Stop
pulse
Logic = 4
Ctrl sgn 1 = Forward
pulse (edge)
Ctrl sgn 2 = Reverse
pulse (edge)
Logic = 5
Ctrl sgn 1 = Start
pulse (edge)
Ctrl sgn 2 = Reverse
pulse
Logic = 6
Ctrl sgn 1 = Start
pulse (edge)
Ctrl sgn 2 = Enable
pulse