MULTI-STEP SPEED CONTROL APPLICATION
Table 26: Input signals, G2.2
Index
Parameter
P2.2.9
AI2 signal selec-
****
tion
P2.2.10
AI2 signal range
AI2 custom set-
P2.2.11
ting minimum
AI2 custom set-
P2.2.12
ting maximum
AI2 signal inver-
P2.2.13
sion
AI2 signal filter
P2.2.14
time
Reference scaling
P2.2.15
minimum value
Reference scaling
P2.2.16
maximum value
Free analogue
P2.2.17
input, signal
selection
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
Min
Max
Unit
0.1
E.10
0
2
-160.00
160.00
%
-160.00
160.00
%
0
1
0.00
10.00
s
0.00
320.00
Hz
0.00
320.00
Hz
0
2
Default
Cust
ID
A.2
388
1
325
0.00
326
100.00
327
0
328
0.10
329
0.00
303
0.00
304
0
361
VACON · 79
Description
TTF programming
method used. See
Chapter 8.9 "Termi-
nal to function" (TTF)
programming princi-
ple.
0 = 0-10V (0-20
mA**)
1 = 2-10V (4-20
mA**)
2 = Custom setting
range**
Analogue input 2
scale minimum.
Analogue input 2
scale maximum.
Analogue input 2 ref-
erence inversion
yes/no.
Analogue input 2 ref-
erence filter time,
constant.
Selects the fre-
quency that corre-
sponds to the min.
reference signal.
Selects the fre-
quency that corre-
sponds to the max.
reference signal.
0.00 = No scaling
>0 = scaled max.
value
0 = Not used
1 = AI1
2 = AI2
4