Table 71: Motor control parameters, G2.6
Index
Parameter
P2.6.15
Load drooping
P2.6.16
Identification
NXP drives only
P2.6.17
Restart delay
Load drooping
P2.6.18
time
Negative fre-
P2.6.19
quency limit
Positive frequency
P2.6.20
limit
Generator torque
P2.6.21
limit
Motoring torque
P2.6.22
limit
* = Parameter value can only be changed after the AC drive has been stopped.
NOTE!
Depending on the application version, the parameter code may appear as 2.6.17.xx
instead of 2.6.23.xx
6
Min
Max
Unit
0.00
100.00
%
0
1/4
0.100
60000
s
0
32000
ms
-327.67
P2.6.20
Hz
P2.6.19
327.67
Hz
0.0
300.0
%
0.0
300.0
%
MULTI-PURPOSE CONTROL APPLICATION
Default
Cust
ID
0.00
620
0
631
Varies
1424
0
656
-327.67
1286
327.67
1285
300.0
1288
300.0
1287
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205
Description
The drooping func-
tion enables speed
drop as a function
of load. Drooping
will be defined in
percent of nominal
speed at nominal
load.
0 = No action
1 = Identification
w/o run
NXP:
2 = Identification
with run
3 = Encoder ID
Run (PMSM)
4 = Ident All
OL delay for coast-
ing stop.
For dynamic
changes.
Alternative limit
for negative direc-
tion.
Alternative limit
for positive direc-
tion.
The maximum tor-
que limit of the
generating side.
The maximum tor-
que limit of the
motoring side.